HMI SETTING

94
HMI SETTING
Administrator Settings 1
In Administrator Settings 1, you can set the basic options necessary for product operation.
1. Set Control Temperature Conditions
Set the conditions of the desired temperature.
The conditions of the desired temperature can be adjusted by using the ventilation and supply
temperatures.
- Ventilation Temperature Conditions
- Supply Temperature Based (when capacity control is used)
- The default control setting is 'Ventilation', but it will change to 'Supply' if a ventilation temper-
ature sensor is not installed.
- The conditions for cooling/heating temperature and humidity will change according to the
Control Temperature conditions.
- The temperature display conditions will be changed to 'Desired (Ventilation)' or 'Desired (Sup-
ply)' in the Details page according to the Control Standard Settings.
- A warning message will appear if the control standard is set to Ventilation without a ventila-
tion temperature sensor installed.
!
CAUTION
• A Capacity Control Communication Cable must be connected when 'Supply' is used as the
Control Temperature standard. A communication error will be created if the Capacity
Control Communication Cable is not connected when it's controlled based on the supply.
Also set the Control Temperature standard to 'Ventilation' if Capacity Control is not used.
Select same as the box on the left side of the
ventilation unit when configuring the settings
based on the ventilation temperature.
Select same as the box on the left side of the
supply unit when configuring the settings
based on the supply temperature.