7.2.4 Events
Visual Display
Events
Deletion
7.2.5 Tools
Battery test
Batteries
Tests the luminous signals. Press 'ENTER' to carry out the test on the signals of the status indicator
Test Display (*)
(blue, violett and red) and the acoustic signals
Tests the alphanumeric display. By pressing 'ENTER' all the characters available on the
LCD-Display Test
alphanumeric display are shown.
(*) Only available in „SERVICE-MODE".
Identification code
Service
Code input
delete all stored faults inside Power module
CM-fault restore
Tri Power X33 Mod HP Manual | Rev 1.20 | © Alpha Technologies GmbH 2013
Tri Power X33 Mod HP
All
Displays all the events
Critical
Displays events thta have generated critical alarms
warning
Displays events that have generated non critical
alarms
Info
Displays events that have generated simple informati-
on
All
Deletes all the events
Manual
the folloewing parameters can be setted:
- nubers of Power modules included inside test
- battery voltage the test stops
-with ENTER the test will start
- with ESC the test will be canceled
Batt. Calibration
Calibrates the batteries, measuring the run down curve.
If the battery is
changed, we recommend carrying out this cycle so that
the UPS provides
precise information about the charge status
Battery Cycle
Carries out a run down and recharge cycle so as to assess
the dynamic
behaviour of the batteries
on request of service department the code has to be given for informati-
on
on request of service please type in the given code