Alpha Technologies Alpha Continuity 6K User Manual

Advertisement

Quick Links

Alpha Continuity 6K / 10K Battery Pack

User Manual

Document #: 0320008-J0
Effective 04/2012

Advertisement

Table of Contents
loading

Summary of Contents for Alpha Technologies Alpha Continuity 6K

  • Page 1: User Manual

    Alpha Continuity 6K / 10K Battery Pack User Manual Document #: 0320008-J0 Effective 04/2012...
  • Page 3 This document, the software it describes, and the information and know-how they contain constitute the proprietary, confidential and valuable trade secret information of Alpha Technologies, and may not be used for any unauthorized purpose, or disclosed to others without the prior written permission of Alpha Technologies.
  • Page 4: Table Of Contents

    Contents Important Safety Instructions....................... 1 Rear Panel Components ........................3 Installation and Operation ........................4 3.1. Unpacking ............................. 4 3.2. Selecting an Installation Position ....................5 3.3. Installation of Rack/Tower kits ..................... 6 3.3.1. Tower Installation – Combined with UPS ................6 3.3.2.
  • Page 5: Important Safety Instructions

    Important Safety Instructions Save These Instructions This section contains important instructions that must be followed during the installation and maintenance of the equipment and batteries. Read all of the instructions before operating the equipment, and save this manual for future reference. The following safety symbol is found throughout this manual: Carefully read all information and abide by the instructions.
  • Page 6     CAUTION:  Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the  battery manufacturer’s instructions.   This battery pack is intended to be connected to an UPS. There will be a DC voltage at the connector terminals.  Do not try to repair the unit yourself, contact your local supplier or your warranty will be void. ...
  • Page 7: Rear Panel Components

    Rear Panel Components Electrical Battery connector Page 3 0320008-J0 Rev B...
  • Page 8: Installation And Operation

    Installation and Operation Note: The packing condition and the exterior of the unit should be inspected carefully before installation. Retain the packing material for future use. 3.1. Unpacking WARNING: The battery pack module is 54.2 to 65.2 kgs (119 to 143 lbs); be cautious when unpacking and lifting the unit to avoid injury.
  • Page 9: Selecting An Installation Position

    3.2. Selecting an Installation Position The battery cable is 8 inches long. Plan to install the battery pack within 3 to 4 inches from the UPS or another battery pack. Select an environment for the unit that will minimize the possibility of damage to the battery pack and extend the life of the batteries: 1.
  • Page 10: Installation Of Rack/Tower Kits

    3.3. Installation of Rack/Tower kits 3.3.1. Tower Installation – Combined with UPS STEP 1 STEP 2 BATTERY Page 6 0320008-J0 Rev B...
  • Page 11: 3.3.2. Rack Mount Installation

    3.3.2. Rack Mount installation STEP 1 B1 B2 S4 B1 B3 S4 STEP 2 Page 7 0320008-J0 Rev B...
  • Page 12: Installation Procedure

    3.4. Installation Procedure STEP 1 RS23 2 OUTPUT INPUT Ext. Batte ry N2 2 L2 1 L1 2 CB 1 Uti lity Inp ut Bre aker To UPS Batte ry First Battery Bank To Exte nde d Ba ttery DC Breaker 30A 250V dc To UPS Batte ry To Exte nde d Ba ttery...
  • Page 13: Batteries

    Batteries 4.1. Battery Pack Discharge Times Table 1 Continuity 6K – 7Ah/12V (x 20pcs) Load (W) 1x BP Continuity 2x BP Continuity 3x BP Continuity 4x BP Continuity 1080 0:42:48 1:30:56 2:16:25 3:01:53 1620 0:25:48 1:03:30 1:41:13 2:14:57 2700 0:12:26 0:41:53 1:02:50 1:29:01...
  • Page 14: Specification

    Specification Continuity 6000VA Continuity 10000VA Battery Pack Model BP Continuity 6K BP Continuity 10K Part Number 0320007-001 0320008-001 Nominal System 240VDC 240VDC Voltage Dimensions W x D x H, mm Unit 440 x 680 x 132 Shipping 560 x 804 x 272 Weight, kg Unit 54.2...
  • Page 16 Fax: +55 11 2476 0150 Fax: +370 5 210 5292 Fax: +852 2199 7988 Due to continuing product development, Alpha Technologies reserves the right to change specifications without notice. Copyright ©2012 Alpha Technologies. All rights reserved. Alpha® is a registered trademark of Alpha Technologies.