4.5
If it weighs less than 30 kg (check on the transport document) the equipment can be moved around by hand as it has two
wheels.
Do not forget that the equipment must always be handled by trained personnel, equipped with the Individual Protective
Gear as specified in Chapter 3.
If the equipment needs to be lifted, use a forklift truck or transpallet of a suitable capacity, inserting the forks in the
wooden base, making sure they come through on the opposite side by at least twenty centimetres.
4.6
The UPS must be placed observing the following conditions:
humidity and temperature must be within the prescribed limits;
the fire protection regulations must be observed;
wiring must be of easy execution;
the front and rear must be accessible for assistance or routine maintenance;
the flow of cooling air must be guaranteed;
the air conditioned system must be adequately sized
there must be no corrosive/explosive gases;
the premises must be free from vibrations;
the clearance at the back and sides must guarantee adequate circulation of the cooling air.
Minimum clearances
recommended UPS
X=100 mm / Y=200 mm
Minimum clearances
recommended UPS +
BATTERY
X=100 mm / Y=200 mm
INDICATION
Bear in mind that the average life of the batteries is strongly influenced by the environmental operating temperature.
Place the unit on premises where the temperature ranges between +18°C (64.4°F) and +23°C (73.4°F) which will guaran-
tee a very long battery life.
Tri Power X33 Mod HP Manual | Rev 1.20 | © Alpha Technologies GmbH 2013
Handling
ATTENTION
Handle with great care, lifting it only to the extent necessary, keep it well balanced and avoid swinging which could
be dangerous.
Positioning
X
Y
UPS
X
BATTERY
BATTERY
Tri Power X33 Mod HP
X
Y
UPS
27