Description
3.4 Options
The standard version of the drive is equipped with a PROFINET interface (slave). The
CP320-2DP Control Unit (option K90) is required to connect to the third-party bus system. The
X gateway is connected to the CU320-2 Control Unit via a PROFIBUS cable. The option is
supplied with a null modem cable for configuring the X gateway. The gateway is preconfigured
to 20 bytes of I/O data. The data size is changed via the configuration interface from a PG/PC
(standard PC tool "Windows Hyper Terminal").
Use the "NetTool" supplied by HMS Industrial Networks to configure PROFIBUS. The NetTool
is not included in the scope of supply.
3.4.27

Modbus Ethernet interface (option G28)

The "Anybus-X-Gateway" supplied by HMS Industrial Networks is used to link the converter
to the Modbus Ethernet bus system.
3.4.28

1x temperature sensor evaluation unit TM150 (option G51)

This option comprises a temperature sensor evaluation unit TM150.
3.4.29

2x temperature sensor evaluation units TM150 (option G52)

This option comprises two temperature sensor evaluation units TM150.
3.4.30

3x temperature sensor evaluation units TM150 (option G53)

This option comprises three temperature sensor evaluation units TM150.
3.4.31

4x temperature sensor evaluation units TM150 (option G54)

This option comprises four temperature sensor evaluation units TM150.
Terminal Module TM150 is used for sensing and evaluating several temperature sensors.
Terminal Module TM150 is designed to connect a maximum of 12 temperature sensors.
For more information, see document "Supplementary component descriptions".
3.4.32

Terminal Module TM31 (option G61)

The standard version of the converter includes a Terminal Module TM15. The Terminal Module
is used for the following functions:
● Inclusion of warning and fault messages and control signals.
● Communication with a higher-level control level.