Terminal Strip Speed Reference Source - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

P.008

Terminal Strip Speed Reference Source

Parameter Range: 0 = Analog Reference (digital inputs 6, 7, and 8 are not used) See P.007
1 = MOP selection (uses
2 = Two (2) preset speeds (uses terminal strip dig. input 6, inputs 7 and 8 left free)
3 = Four (4) preset speeds (uses terminal strip dig. inputs 6 and 7, input 8 left free)
4 = Eight (8) preset speeds (uses all terminal strip digital inputs)
5 = Analog Reference and one (1) preset speed (Uses digital input 6, inputs 7 and 8
6 = Analog Reference and three (3) preset speeds (Uses digital inputs 6, 7, input 8 is
7 = Analog Reference and seven (7) preset speeds (Uses digital inputs 6, 7 and 8)
Initial Setting:
0 = Analog Reference
Type:
Configurable (in standby only)
Refer to:
P.007 Terminal Strip Digital Inputs Configure,
R.030 Digital Input Configuration
Description:
This parameter selects the source of the terminal strip speed reference.
The terminal strip speed reference is used when:
• the terminal strip is the selected control source (P.000 = rE), or
• the local keypad or serial port is the selected control source (P.000 = LOCL or
In selections 5, 6 and 7, a digital input will initiate the selected preset speed which will
override the analog speed reference. Refer to table 4-2 in the P.031 parameter
description.
The selection is dependent upon what is selected for parameter P.007.
The selection made in parameter P.007 determines what the remaining free digital
inputs can be used for. See Table 4-1 for acceptable combinations.
P.007
Selections
0
1
2
3
4
5
6
7
8
9
10
11
12
Table 4-1. Acceptable P.007 and P.008 Selection Combinations.
P.007 and P.008 Selection Example:
• If you want to select the MOP as the speed reference source P.008 must be set to 1.
• Next select the value for P.007 using table 4-1. Following the column down under P.008,
selections the acceptable selections for P.007 are 4,5,6, 7 or 12.
For use with RMI option card refer to RMI-Manual 49'1330
4 - 10
4 - GENERAL PARAMETERS, DESCRIPTION
are not used)
not used)
SErL) and AUTO is selected (AUTO LED is on).
P.008 Selections
0
1
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
digital input 6 for the MOP increment function,
digital input 7 for the MOP decrement function,
digital input 8 is not used)
2
3
4
!
!
!
!
!
!
GV3000/SE
P.031 Preset Speed 1
5
6
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
7
!
49'1329 e

Advertisement

Table of Contents
loading

Table of Contents