Programming Disable; Auto/Man Key Disable - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

P.051

Programming Disable

Parameter Range: 0 - 9999
Password:
26
Initial Setting:
0 (Programming enabled)
Type:
Tunable (at rest or during operation)
Description:
When the password is entered into this parameter, parameter values cannot be
modified from the keypad unless the correct password (26) is entered again. Refer
to section 3 'Programming Disabling / Enabling' of this manual for more information
To disable parameter programming:
1.
2.
3.
4.
5.
To return back to enable programming, re-enter the password by repeating the
steps above.
WARNING: It is the user's responsibility to determine how to distribute the
password. Rockwell Automation is not responsible for authorized access violations
within the user's organization. Failure to observe this precaution could result in
bodily injury.
P.052

AUTO/MAN Key Disable

Parameter Range: OFF = Enable the AUTO/MAN key regardless of control source
ON = Disable the AUTO/MAN key except from the selected control source
Initial Setting:
OFF
Type:
Tunable (at rest or during operation)
Refer to:
P.000 Control Source,
Description:
This param. disables the AUTO/ MAN key except from the selected control source.
When this parameter is set to ON, the AUTO/MAN key is functional only from the
selected control source. This parameter can be used to protect against inadvertent
reference change when the drive is controlled from the terminal strip (P.000 = rE) or
the option port (P.000 = OP).
The following Table details whether the AUTO/MAN key is active based on the
selected control source and P.052.
Control Source (P.000 =)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
Note that if P.000 = rE, but the REMOTE/LOCAL switch at terminal 17 is set for
LOCAL (closed), the AUTO/MAN key is active even if P.052 is set to ON.
49'1329 e
4 - GENERAL PARAMETERS, DESCRIPTION
Access P.051 on the display.
Press the ENTER key. Display shows "0".
Increment the value to 26.
Press the ENTER key. Display shows "P.051".
The PASSWORD LED will be on to indicate parameters cannot be modified
from the Keypad.
P.053 Manual Reference Preset Enable
P.052
Front Panel
AUTO/MAN Key
OFF
OFF
OFF
OFF
ON
ON
ON
ON
GV3000/SE
OIM/CS3000
AUTO/MAN Key
Active
Inactive
Active
Active
Inactive
Active
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Active
Active
Active
Active
4 - 29