P.009

Terminal Strip Analog Input Offset

Parameter Range: -900 to +900 (For 0 to 10 V input, a value of +1 equals an offset of approx. 10mV.)
Initial Setting:
0
Type:
Tunable (at rest or during operation)
Refer to:
P.000 Control Source
Description:
This parameter allows for correcting any offset in the terminal strip analog input
prior to the signal reaching the drive.
Verify that the analog input is configured as the speed reference control source
(P.000 = rE or LOCL and AUTO is selected), P.008 = 0, and U.000 = 0).
Note: This parameter is not used if the terminal strip analog input is used as vector torque
reference (U.000 = 1). See Vector Regulator Speed Loop, Figure 6-1a.
P.010

Terminal Strip Analog Input Gain

Parameter Range: 0.100 - 5.000
Initial Setting:
1.000
Type:
Tunable (at rest or during operation)
Refer to:
P.000 Control Source
Description:
This parameter is used to compensate for component tolerance errors or insufficient
voltage from the input reference source at the terminal strip.
Note: This parameter is not used if the terminal strip analog input is used as vector torque
reference (U.000 = 1). See Vector Regulator Speed Loop, Figure 6-1a.
P.011

Terminal Strip Analog Input Configure

Parameter Range:
49'1329 e
4 - GENERAL PARAMETERS, DESCRIPTION
Jumper J4 on pins
2 and 3
Jumper J4 on pins
1 and 2
Jumper J4 on pins
2 and 3
0 = +/- 10 VDC
1 = +/- 10 VDC inverted
2 = 0 to 10 VDC
3 = 0 to 10 VDC inverted
4 = 4 to 20 mA. Generate fault on signal loss.
5 = 4 to 20 mA inverted. Generate fault on signal loss.
6 = 0 to 20 mA
7 = 0 to 20 mA inverted
8 = 4 to 20 mA. Display alarm and use previous
reference on signal loss.
9 = 4 to 20 mA inverted. Display alarm and use previous
reference on signal loss.
10 = 4 to 20 mA. Display alarm and use Preset Speed 1
(P.031) as reference on signal loss.
11 = 4 to 20 mA inverted. Display alarm and use Preset
Speed 1 (P.031) as reference on signal loss.
12 = 0 to 10 VDC. Start and stop the drive based on
analog input value. (P.000 must be set to rE.)
GV3000/SE
4 - 11