Gv3000/Se Regulator, V/Hz Mode Parameters (H.xxx) - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

GV3000/SE Regulator, V/Hz Mode Parameters (H.xxx)

* = Parameter tuneable at drive stopped or running; all others adjust with drive stopped.
Para-
Description
meter
V/Hz control mode only
H.000
Motor Nameplate Volts
(1)
H.001
Mot. Namepl. Base Frequency
H.002
Motor Nameplate Amps
H.003
Torque Boost Voltage
*H.004
Slip Compensation
*H.005
D-C Braking Enable
*H.006
D-C Braking Start Frequency
*H.007
D-C Braking Current
*H.008
D-C Braking Time
*H.009
Avoidance Frequency Enable
*H.010
Avoidance Freq. 1, Midpoint
*H.011
Avoidance Frequency 1, Band
*H.012
Avoidance Freq. 2, Midpoint
*H.013
Avoidance Frequency 2, Band
*H.014
Avoidance Freq. 3, Midpoint
*H.015
Avoidance Frequency 3, Band
H.016
Sync. Direction
(4)
(Start into rotating motor)
GV3000/SE
(
motor RPM starting at max.
frequency and synchronizes its
reference)
H.017
Input Power/ Snubber
Configuration
H.018
V/Hz Curve Type
H.019
Identification Result
(6)
(Output Variable only)
H.020
Identification Request
(1)(6)
H.021
A-C Line Voltage
(10)
H.022
Overfrequency Limit
Notes: (1) P.047, P.005 and H.000 must be set before activating at V/Hz mode the Identification Request (H.020)
(4) Don't set H.016 (Sync. Mode Select) to any value but 'F' avoiding REVERSE rotation via P.027 (Reverse Disable)
(6) See Section 5 for Identification Request Result Procedure.
(10) See Section 2, Table 2-5, Note 1) of power units manual 49'1327, if the internal Braking Unit option is provided.
49'1329 e
8 - PARAMETER QUICK REFERENCE GUIDE
Selection / Adjustment Range
180 - 690 VAC
30.0 -200.0 Hz (frequency at nominal voltage)
Power module-dependent
0.0 - 20.0% of nominal motor voltage
0.0 - 10.0% of base frequency (H.001) added to freq. ref.
OFF - Disable DC Braking
ON - Enable DC Braking
0.5 Hz - Value in P.004 (Maximum Hz) in Hz
0.0% - 100.0% of Motor Nameplate Amps
0.0 - 10.0 s
OFF - Disable avoidance freq., 'ON' - Enable avoid. freq.
0.0 - 200.0 Hz
2.0 -
10.0 Hz
0.0 - 200.0 Hz
2.0 -
10.0 Hz
0.0 - 200.0 Hz
2.0 -
10.0 Hz
OFF - Disable Synchronisation (fx = max.freq.)
F
- Searching starts at +fx (forward)
r
- Searching starts at -fx (reverse)
searches
Fr
- Searching starts at +fx, then at -fx
rF
- Searching starts at -fx, then at +fx
0= AC input with bus-regulator, with ride-thru enabled
1= AC input w/o bus-regul., with ride-thru a. Dyn. Braking
2= DC input with bus-regul., w/o ride-thru (System 1-Q)
3= DC input w/o bus-regul., w/o ride-thru (System 4-Q)
4= DC input with bus-regul., with ride-thru (Single drive)
5= DC input w/o bus-regul., with ride-thru and Dyn. Brak.
0 - Linear V/Hz curve
1 - Optimized curve for 'RPM AC' motors
2 - Squared V/Hz curve
0 = Ident. Procedure successful
1 = Logged error aborted Ident. Procedure
2 = Function Loss aborted Ident. Procedure
3 = STOP command aborted Ident. Procedure
4 = Current feedback too low. Ident. aborted.
6 = Result out of range. Ident. aborted.
OFF - Disable Identification Procedure
ON - Enable Identification Procedure
300- 565 VAC
(enter value within +/-10% of actual line voltage)
30.0 - 4 x H.001 +5% or 210 Hz
GV3000/SE
N/A = not available
EUr-Init.
Setting
380VAC
50.0 Hz
P/U dep.
0.5%
0.0%
OFF
1.0 Hz
10%
3.0 s
OFF
0.0 Hz
2.0 Hz
0.0 Hz
2.0 Hz
0.0 Hz
2.0 Hz
OFF
0
0
N/A
OFF
380 VAC
(on type V/Hz)
90 Hz
Actual
Setting
8 - 5