Country Defaults; Restore Defaults - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

V/Hz or Vector Mode Regulation (continued)
Sensorless vector control (SVC) is an extension of the FVC regulator. It provides
performance close to FVC without using an encoder. Control is based on estimated
speed feedback. You program the drive for SVC by first selecting UEC in parameter
U.048 and then selecting SE in parameter U.001 (Encoder PPR).
In vector control mode an Outer Control Loop (OCL) is also available.
The OCL executes every 20 ms.
Switching from one regulator type to the other will take approximately 5 to 10
seconds. The drive will re-initiate power-up diagnostics (SELF will appear on the
display and all LEDs will turn on for approximately 4 seconds).
Changing this parameter will also restore default values for all First and Second
Menu General parameters (P.---) as if a Restore Defaults command (P.050 = ON)
was given. However, this will NOT change the value of P.048 or P.049 (Country
Defaults).
Important: All other parameter values must be verified if this parameter is changed after initial
programming, regardless of whether they are restored to their default values
P.049

Country Defaults

Parameter Range: USA = U.S.A
EUr =
JPn =
Initial Setting:
EUr
USA
Type:
Configurable (in standby only)
Description:
This parameter selects the factory default settings for the First and Second Menu
General parameters. European default settings are listed throughout Sections 5 to
7 and 9 of this manual. Refer to I/M D2-3427 or D2-3359, Section 4 for the U.S.A.
and Appendix E for Japanese default settings.
P.050

Restore Defaults

Parameter Range: OFF = No Action
ON = Reset P.--- parameters to default settings
Initial Setting:
OFF
Type:
Configurable (in standby only)
Refer to:
P.048 V/Hz or Vector Mode Regulation
P.049 Country Defaults
Description:
This parameter resets all First and Second Menu General (P.---) and (r.---)
parameters to the default settings (with exception of P.048 and P.049) according to
Country Defaults (P.049) and V/Hz or Vector Mode
After the par. values have been restored, P.050 will automatically be reset to OFF.
4 - 28
4 - GENERAL PARAMETERS, DESCRIPTION
Default Settings
European Default Settings
Japanese Default Settings
(for deliveries from European subsidiaries of Rockwell Automation)
(for deliveries from American subsidiaries of Rockwell Automation)
GV3000/SE
(
P.048).
49'1329 e