Option Port: Network Trim Reference Source; Option Port: Type And Version - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

P.064

Option Port: Network Trim Reference Source

Parameter Range: Option port dependent
Default Setting:
0
Parameter Type:
Configurable
Refer to:
P.063 Option Port: Network Reference Source
U.000 Torque Reference Source.
Description:
This parameter selects where the drive gets its trim reference when the option port
is selected as the control source (P.000 = OP). The option port trim reference is
used as the outer control loop reference and/or the speed trim reference when
P.014 (Trim Reference Source) = 2.
In V/Hz regulation, the trim reference represents speed in hertz scaled 0 to 4095 for
0 to Maximum Speed (P.004).
In vector regulation, the trim reference represents speed scaled 0 to 4095 for 0 to
Top Speed (U.017). When used for the outer control loop, the value should be
scaled based on the scaling of the selected feedback
Refer to the specific network board instruction manual for more information on P.064.
If a network board is installed, the OCL reference comes from the network trim reference register
based on P.064 (Option Port: Network Trim Reference Source) as defined for each network type.
If a RMI board is installed, P.064 is used to select the OCL reference as follows for FVC/SVC
applications only:
0 = RMI analog input
1 to 8 = Preset speed 1 to 8 (P.031 to P.038), respectively
If no option board is installed, P.064 is used to select the OCL reference for FVC/SVC applications only:
0 = Preset speed 8 (P.038)
1 to 8 = Preset speed 1 to 8 (P.031 to P.038), respectively
P.065

Option Port: Type and Version

Parameter Range: N/A
Default Setting:
N/A
Parameter Type:
Output (read only)
Description:
The display format is N.vvv, where N represents the option driver type
and vvv represents the software version number of the option port.
For example, if 2.115 is displayed, it means the drive is using the DeviceNet
network option running software version 1.15.
49'1329 e
4 - GENERAL PARAMETERS, DESCRIPTION
InterBus Network Communication
Profibus DP Network Communication
AutoMax Network Communication
DeviceNet Network Communication
ControlNet Network Communication
Remote Meter Interface RMI
1.vvv = RMI Option
2.103 = AutoMax network Option,
2.100 = InterBus network Option,
2.11v = DeviceNet network Option,
2.7vv = Profibus network Option,
5.vvv = ControlNet network Option
49'1333
49'1355
D2-3308
MAN0096-03
D2-3390
49'1330
GV3000/SE
4 - 35