P.090

Diagnostics Source

Parameter Range: 0 - 19
Default Setting:
0
Parameter Type:
Tunable (at rest or during operation)
Refer to:
P.091 Diagnostics Display
Description:
This parameter is used to select, internal information such as I/O data, network
statistics, etc., for display in parameter P.091.
10 = Regulator Board terminal Analog Input with P.009 applied
11 = Analog Input stop threshold
12 = Analog Input start threshold
14 = Network interface: number of messages received from the network
15 = Network interface: number of message receive time-out errors
16 = Network interface: number of message CRC errors
17 = Network interface: number of message overrun errors
18 = Network interface: number of messages aborted
19 = Network interface: number of messages transmitted to the network
If P.090 = 11 the analog input stop threshold is selected for viewing and modifying in P.091.
The stop threshold ranges from 5 to 1023 and defaults to 20, which corresponds to 0.20 VDC
(nominally) when the Power Module is identified (P.998/P.999).
If the stop threshold is greater than the start threshold, the stop will take precedence.
In other words, if the analog input is less than or equal to the stop threshold, the drive will stop
regardless of the start threshold.
If P.090 = 12 the analog input start threshold is selected for viewing and modifying in P.091.
The start threshold ranges from 0 to 2000 and defaults to 30, which corresponds to 0.33 VDC
(nominally) when the Power Module is identified (P.998/P.999).
Note that the default threshold values are not restored when P.050 (Restore Defaults) is set to ON.
49'1329 e
4 - GENERAL PARAMETERS, DESCRIPTION
1 = Regulator Board terminal strip Digital Inputs 4, 3, 2, 1:
The value is a four digit combination of 1s and 0s.
P.091= Run/Jog * 1000 + Reset * 100 + Stop * 10 + Start
2 = Regulator Board terminal strip Digital Inputs 8, 7, 6, 5:
The value is a four digit combination of 1s and 0s.
P.091= DIN_8 * 1000 + DIN_7 * 100 + DIN_6 * 10 + FN_LOSS
3 = Regulator Board Terminal Analog Input:
P.091= The value displayed is after offset and gain
4 = RMI Digital Inputs 4, 3, 2, 1:
The value is a four digit combination of 1s and 0s.
P.091= R_DIN_4 * 1000 + R_DIN_3 * 100 + R_DIN_2 * 10 + R_DIN_1
5 = RMI Board Analog Input:
P.091= The value displayed is after offset and gain
6 = RMI Frequency Input:
P.091= The value displayed is after offset and gain
7 = Encoder data
8 = DC bus voltage
9 = Regulator Board terminal Analog Input scaled
GV3000/SE
4 - 37