Network Output Register 1 Source; Network Output Register 4 Source; Signal Selection For Network Output Registers - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

P.066 to
Network Output Register 1 Source through
P.069

Network Output Register 4 Source

Parameter Range:
10 = Regulator Board Terminal analog input scaled
11 = Torque reference*
12 = Torque feedback*
∗ ∗ ∗ ∗
Default Setting:
0
Parameter Type:
Tunable (at rest or during operation)
Description:
These parameters select the signal written to the option port network output
registers 1 through 4.
Refer to the Option board instruction manual (D2-3308) for the AutoMax network
register map or to the Option Board instruction manual (D2-3390) for ControlNet for
ControlNet register map.

Signal Selection for Network Output Registers

4 - 36
4 - GENERAL PARAMETERS, DESCRIPTION
0 = (P.066) Motor kW display value
(P.067) Motor torque display value*
(P.068) Output power factor
(P.069) Encoder counter (x4)*
1 = Speed reference rate limit output*
2 = Speed reference at the ref/fdbk summing junction
(includes OCL output and current compounding)*
3 = Speed loop feedback*
4 = Speed loop error*
5 = Speed PI output*
6 = Outer control loop feedback*
7 = Outer control loop error*
8 = Outer control loop output*
9 = Regulator Board Terminal analog input normalized to speed
(see Regulator Block Diagram Figure 6-1a)
(see Regulator Block Diagram Figure 6-1a)
These signals are valid only in vector control (P.048 = UEC).
P.066
0 = Motor KW
display value
.
.
.
12
P.067
0 = Motor torque
display value
.
.
.
12
P.068
0 = Output power
factor
.
.
.
12
P.069
0 = Encoder
counter (x 4)
.
.
.
12
Network Module
Network Output Register 1
Network Output Register 2
Network Output Register 3
Network Output Register 4
GV3000/SE
49'1329 e