Terminal Strip Digital Inputs Configure; General Parameters, Second Menu List - Reliance electric GV3000/SE Instruction Manual

General purpose and vector drive
Table of Contents

Advertisement

GENERAL PARAMETERS - Second Menu List (P.007 to P.099)
P.007
Parameter Range:
Type:
Refer to:
Initial Setting:
Description:
If a maintained START contact is used in REMOTE mode, switching from LOCAL to REMOTE
will cause the controller to start and the motor will rotate, if the remote START contact is closed.
Stay clear of rotating machinery. Failure to observe this precaution could result in bodily injury.
The GV3000/SE drive provides multiple configurations of digital inputs 6,7, and 8 on the terminal strip.
This parameter determines how these inputs are used.
The P.008 (Terminal Strip Speed Reference Source) will limit the selection of P.007 because the P.008
selection may use one or more digital inputs 6 through 8. Selections 8 through 12 apply to vector
regulation only.
An unasserted (open) or asserted (closed) input will select the following of the four input choices:
Input
FWD/REV
RAMP1/2
REM/LOC
TRQ/SPD
FWD/REV allows you to select between forward or reverse operation. If the Input is closed this function
will invert the selected speed reference. For example If the selected speed reference value is
negative (<0), the FWD/REV input is closed (which allows reverse direction), and reference is not
inverted (P.011=OFF), the resulting speed reference will be positive (forward).
NOTE: Forward means clockwise rotation viewing motor drive end, with the following conditions:
European motor and U,V,W of the Inverter connected to U,V,W of the motor at Forward
mode (Refer to P.007) and positive speed reference selected (Refer to P.008, P.011).
RAMP1/2 allows you to select between one of two paired acceleration/deceleration rates. Ramp 1 uses
accel or decel rates based on P.001/P.002. Ramp 2 uses accel or decel rates based on
P.017/P.018. ( for RUN only, for JOG refer to P.021, P.022).
NOTE: The digital input for RAMP1/2 is always active regardless of the control source.
4 - 8
4 - GENERAL PARAMETERS, DESCRIPTION

Terminal Strip Digital Inputs Configure

Digital Input 6:
(Terminal 19)
0 =
FWD/REV
1 =
2 =
3 =
4 =
5 =
6 =
7 =
not used
8 =
FWD/REV
9 =
not used
10 =
not used
11 =
not used
12 =
not used
Configurable (in standby only)
P.008 Terminal strip Speed Reference Source
0
Open = OFF (0V)
Forward
Ramp 1
Remote
Torque
Digital Input 7:
Digital Input 8:
(Terminal 18)
(Terminal 17)
RAMP1/2
REM/LOC
FWD/REV
RAMP1/2
FWD/REV
REM/LOC
RAMP1/2
REM/LOC
FWD/REV
RAMP1/2
REM/LOC
not used
not used
TRQ/SPD
REM/LOC
TRQ/SPD
REM/LOC
TRQ/SPD
FWD/REV
TRQ/SPD
RAMP1/2
not used
TRQ/SPD
WARNING
Closed = ON (24V)
Reverse
Ramp 2
Local
Speed
GV3000/SE
49'1329 e