Control Voltage Output, Digital Inputs

(see wiring diagram for Remote Terminal Block)
Terminals
Connected function
J1:
16
+24 V Control voltage output, isolated, current limited. This supply should not be used
as an external supply for anything other than the 8 digital inputs.
25
24 V Control voltage Common
20
Function Loss (dig. input no. 5)
0 V at terminal = Function Loss active
+24 V at terminal = Drive enabled
- Function Loss is effective in all control modes (P.000: LOCAL, REMOTE, etc.)
and has priority over start
- Function Loss Restart Procedure with P.026 = 0 :
* Speed reference is zero, motor coasts to rest,
* error code 'FL' is displayed,
* output relay will pick up if configured (P.013) for FAULT ACTIVE.
* Remove function loss cause and reset IET using STOP/RESET before restarting.
- Function Loss Restart Procedure with P.026 = 1 :
* Speed reference is zero, motor coasts to rest,
* no error code is displayed,
* output relay will not pick up if configured (P.013) for FAULT ACTIVE.
* Remove function loss cause and restart (no resetting of IET).
23
STOP Command (dig. input no. 2)
-
0 V at terminal = STOP activated
- +24 V at terminal = Drive enabled
- P.025 for type of STOP ('coast to rest' or 'ramp to rest')
- P.055 (STOP/RESET Key Disable) can be used to change the operation of the
STOP/RESET key. See the P.055 parameter description in the Regulator manual.
22
RESET Command (dig. input no. 3)
- Transition to +24V at terminal = RESET IET (Instantaneous Electronic Trip) with error
cause removed.
21
JOG / RUN Selection (dig. input no. 4)
-
0 V at terminal = RUN-Mode selected
- +24 V at terminal = JOG-Mode selected
24
START Command at REMOTE operation mode (dig. input no. 1)
RUN function will be active:
- If
JOG function will be active:
- If
19
Digital Input No.6,
18
Digital Input No.7, and
17
Digital Input No.8 are configurable via P.007 and P.008 (Refer to parameter description in
manual 49'1329, Section 4). P.007 : Initial setting:
No.6 (+24 V)=REVERSE, No.7 (+24 V)=RAMP 2, No.8 (+24 V)=LOCAL.
49'1327 e
RUN selected
No STOP command +24 V at dig. input no.2, and
No Function Loss
START command
JOG selected
No STOP command +24 V at dig. input no.2, and
No Function Loss
START command
3 - INSTALLATION
has priority over start
0 V at dig. input no.4, and
+24 V at dig. input no.5, and
transition to +24 V at dig. input no.1.
+24 V at dig. input no.4, and
+24 V at dig. input no.5, and
+24 V maintained at dig. input no.1.
GV3000/SE
3-7