P.091

Diagnostics Display

Parameter Range: N/A
Default Setting:
N/A
Parameter Type:
Output (read only)
(configurable input, if P.090 is set to 11 or 12)
Refer to:
P.090 Diagnostics source
Description:
This parameter displays the Terminal strip and RMI input data selected in P.090.
The status of the digital inputs (selected by entering a value of 1, 2, or 4 in P.090) is
displayed as a four-digit combination of 1s and 0s (1 = on, 0 = off) in the following
manner:
Selection 1, terminal strip digital inputs
Selection 2, terminal strip digital inputs
Selection 4, RMI digital inputs
P.095

Power Module Output Amps

Parameter Range: N/A, Power Module size dependent
Default Setting:
N/A
Parameter Type:
Output (read only)
Refer to:
P.005 Current Limit
Description:
This parameter displays the maximum output current rating of the drive. The
maximum value of Current Limit (P.005) corresponds to P.095. This parameter is
read only.
For example, if P.095 = 11.0 and P.005 = 110% (its maximum), then the maximum
output current rating with no overload rating (100% rating) = 10.0 amps.
Refer to manual 49'1327 'GV3000 Power Unit' for Nominal Current and Overload
Current values per Power Module size and selected Carrier Frequency (P.047) and
Regulation Mode (P.048).
P.098

Software Version Number

Parameter Range: N/A, Regulator Board dependent
Default Setting:
N/A
Parameter Type:
Output (read only)
Refer to:
N/A
Description:
The parameter displays the software version number.
The value is not adjustable by the user.
4 - 38
4 - GENERAL PARAMETERS, DESCRIPTION
GV3000/SE
Four-Character Display
" " " "
4
3
2
1
8
7
6
5
4
3
2
1
49'1329 e