Gpm5·1 Module - Deif AWC 500 Installation Instruction

Advanced wind turbine controller
Hide thumbs Also See for AWC 500:
Table of Contents

Advertisement

AWC 500 Installation instruction
State
Solid green
Solid orange
Flickering green
Flickering orange/red
Terminals:
Cable:
4.3. GPM5·1 module
The Grid and Protection Module GPM is a class 0.5 grid measurement and protection module which
can be fully configured from the main application. All measurements are available for the main
application each period of the connected grid. The module offers:
• 1 x Current input
• 2 x Voltage inputs
• 2 x Digital relay outputs
• 2 x Digital inputs
Table 7. Run LED:Tri-coloured diode showing the EtherCAT state as well as Service state
State
Off
Blinking green (slow)
Blinking orange/red (slow)
Single Flash green (slow)
Single Flash orange/red
Solid green
Solid orange
Flickering green
Flickering orange/red
4.3.1. Current input
The GPM has one direct three phase current input. The class 0.5 accuracy is kept within each range.
Current range:
Frequency:
Load max.:
Overload:
UL/cUL:
Terminals:
Cable:
4.3.2. Voltage inputs
The GPM offers two direct three phase voltage inputs. The class 0.5 accuracy is kept within each
www.deifwindpower.com
Description
Normal operational
Normal operational, and module selected
Boot loader
Boot loader, and module selected
Spring cage plug-able connectors
2
0.2...1.5 mm
single/multi-stranded wire
Description
INIT or no power
Pre-operational
Pre-operational, and module selected
Safe-operational
Safe-operational, and module selected
Normal operational
Normal operational, and module selected
Boot loader
Boot loader, and module selected
0...1 or 0...5 A
40...70 Hz
0.4 VA per phase
20 A for 60 s, <75 A for 10 s, <300 A for 1 s
From listed or R/C (XODW2.8) current transformers
Screw connection
2
0.2...2.5 mm
single/multi-stranded wire
4.3. GPM5·1 module
Page 11 of 14

Advertisement

Table of Contents
loading

Table of Contents