Deif AWC 500 Installation Instruction
Deif AWC 500 Installation Instruction

Deif AWC 500 Installation Instruction

Advanced wind turbine controller
Hide thumbs Also See for AWC 500:

Advertisement

Quick Links

AWC 500 Installation instruction

Advertisement

Table of Contents
loading

Summary of Contents for Deif AWC 500

  • Page 1 AWC 500 Installation instruction...
  • Page 2: Table Of Contents

    3. System installation ............. . .   3.1. Precautions regarding the ambient temperature of the AWC 500 system .... ...
  • Page 3: Revision

    AWC 500 Installation instruction 1. Revision 1. Revision Revision Author Date Description 2012-07-03 Initial release 2018-03-05 Updated to PCM5·2 www.deifwindpower.com Page 1 of 14...
  • Page 4: Installation Instruction

    This Installation instruction document contains both general and specific information on how to carry out the installation of the AWC 500 system. By observing the advice given in this document, a safe and correct installation of the AWC 500 system is ensured.
  • Page 5 3.2. Installing the Rack Due to air circulation, it is not recommended to place objects within 150 mm from the top and bottom of the Rack. Figure 1. AWC 500 rack dimensions. Table 2. Overall dimensions for rack variants Rack width...
  • Page 6: Recommended Screws/Bolts For Mounting

    Figure 2. Recommended installation clearance. 3.3. Recommended screws/bolts for mounting It is recommended to mount the AWC 500 using a stainless steel M6 screw/bolt and matching plain washer of A2-70 ISO 3506 quality or better. The screw/bolt should be tightened with 5 Nm.
  • Page 7: Ensuring The Awc 500 System's Electromagnetic Compatibility (Emc)

    500 modules within the Rack with power. Furthermore the PCM in used to connect to distributed racks. The Power and Distributed communication Module (PDM) in used is distributed racks to supply the other AWC 500 modules within the rack with power. The module can also be used to connect to further distributed racks.
  • Page 8 AWC 500 system will continue un-interrupted. If power continues to be absent after this blackout protection period the AWC 500 will enter its Safe Shutdown Cycle in which it will assure that all data addressed to the non-volatile memory is securely written.
  • Page 9 All PCM/PDM modules offer two EtherCAT OUT ports (Port 1 and Port 2). These are used to connect directly to other distributed AWC 500 racks with PDM modules or to third party EtherCAT components. The PDM module additionally offers one EtherCAT IN port (Port 0). The ports are either 100Base-TX (twisted-pair) or 100Base-FX (Fibre).
  • Page 10 4.1.4. Ethernet Ethernet at PCM is two standard 1000Base-TX ports that can be used to connect the AWC 500 to a switched Ethernet network. DEIF does not recommend to connected the PCM directly to the Internet, hence it should always be placed behind proper updated and maintained security equipment (firewall etc.) as demanded by the specific use case.
  • Page 11 AWC 500 Installation instruction 4.1. PCM5·2/PDM5·1 module Cabling: Twisted pair cable with shield. The cable must have a characteristic impedance of 120 Ω. The shield of the cable should be connected to GND. End terminations of 120 Ω; can be configured in software.
  • Page 12: Iom5·1 Module

    AWC 500 Installation instruction 4.2. IOM5·1 module Data bits: Stop bits: Parity: None Flow control: None Related to PCM5·2: When connected the service port provides console access to the OS. Related to PDM5·1: When a given module is selected (and the USB cable is connected to a PC), the Run LED on that module overlays its red colour to the currently status of the LED.
  • Page 13: Gpm5·1 Module

    AWC 500 Installation instruction 4.3. GPM5·1 module State Description Solid green Normal operational Solid orange Normal operational, and module selected Flickering green Boot loader Flickering orange/red Boot loader, and module selected Terminals: Spring cage plug-able connectors Cable: 0.2…1.5 mm single/multi-stranded wire 4.3.
  • Page 14: Ifm5·1 Module

    AWC 500 Installation instruction 4.4. IFM5·1 module range. Please note that at altitudes above 2000 m the UL approval limits the input range to a maximum of 520 V. Input range: 0…690 V Measure range: 40…100, 40…240 or 40…690 V Frequency: 40…70 Hz...
  • Page 15: Module Replacement Instructions

    AWC 500 Installation instruction 5. Module replacement instructions Cable: 0.2…1.5 mm single/multi-stranded wire 5. Module replacement instructions 5.1. General precautions Before handling the boards there are a few, but important instructions that must be observed: Throughout the whole process of manufacturing and testing, the products have been kept in static shielding bags, and all personnel handling the products have been protected against static electricity and the subsequent ESD (electrostatic discharge).
  • Page 16 AWC 500 Installation instruction 5.4. Replacing the RTC Battery on the PCM5·2 module Figure 4. Battery for the RTC DEIF A/S reserves the right to change any of the above. www.deifwindpower.com Page 14 of 14...

Table of Contents