15.8 Display indications and software parameters

15.8.1 Status indications
Indication
1st line:
S0
Operation mode
2nd line:
Run commands
3rd line:
Actuator position
4th line:
Current status (only
if no faults or
warnings have
occurred).
If faults or warnings
occur these signals
are indicated in the
4th line.
For indication and operation see page 19, subclause 15.5.2.
VALUETEXT
Note
The operation mode LOCAL - OFF - REMOTE is changed
OFF
with the selector switch.
LOCAL MODE
RESTRICTED: The local controls of the AUMATIC have not
REMOTE MODE
been released yet. A release must be initiated externally via
bus or input signal. See parameter "
MODE
FAILURE MODE
EMERGENCY MODE
RESTRICTED
The digital run commands (OPEN-STOP-CLOSE) can e.g.
OPEN
come from the local controls or from REMOTE.
CLOSE
The run commands are only displayed as long as a com-
STOP
mand is actually active.
If several run commands are active simultaneously, the
OPEN CLOSE
signal '
OPEN STOP
CLOSE STOP
OPEN STOP CLOSE
Actual value of the actuator position (only in case of an actu-
E2######—
al value transmitter e.g. potentiometer or RWG)
Actuator runs logically OPEN (remains set during operation pau-
RUNNING OPEN
ses)
Actuator runs logically CLOSE (remains set during operation
RUNNING CLOSE
pauses)
End position OPEN reached
OPEN POSITION
End position CLOSED reached
CLOSED POSITION
A fault has occurred (fault signals stop the operation); see
FAULT
menu S1
A warning has occurred (warning signals do not influence
WARNING!
operation and serve only information purposes); see menu S2
FAULT AND WARNING Faults as well as warnings have occurred.
The actuator can not be operated from REMOTE.
NOT READY
The actuator can only be operated via the local controls.
Faults and the signal NOT READY have occurred.
FLT + NR!
Warnings and the signal NOT READY have occurred.
WRN + NR!
Faults, warnings and the signal NOT READY have occurred.
FLT + WRN + NR!
Part-turn actuators SG 03.3 – SG 04.3
", page 47.
' is given.
FAULT
with AUMATIC AC 01.1
ENABLE LOCAL