Power Supply Specifications - Mitsubishi Electric A960GOT User Manual

Human machine interface, graphical operator terminal
Table of Contents

Advertisement

3 PERFORMANCE

3.2.3 Power supply specifications

Item
Input power supply voltage
Input frequency
Input max. apparent power
Input max. power
Inrush current
Permissible instantaneous
power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance
External output
Insulation system
Rated load voltage
Operating load voltage
range
Max. load current
Max. inrush current
OFF-time leakage
current
ON-time max. voltage
drop
OFF
ON
Response
time
ON
OFF
Surge suppressor
Applicable wire size
Applicable solderless
terminal
Applicable tightening torque
(Terminal block terminal
screw)
3 - 8
A985GOT-TBA-V
AC100 to 240V (+10,
50/60Hz
59VA or less (Using AC100V)
RS-422, RS-232C, Other
than Bus connection 69VA
74VA or less (Using AC200V)
RS-422, RS-232C, Other
than Bus connection 86VA
40A max. (264VAC, max. load)
20ms (100VAC or more)
By noise simulator of 1,500Vp-p noise voltage, 1µs noise
width and 25 to 60Hz noise frequency
1500VAC for 1 minute across AC external terminals and
earth (2830VAC for 1 second for EU)
Remarks
Please note that resetting will take place if an instantaneous power failure occurs to
the GOT power supply.
However, the monitoring and other functions operate normally if the instantaneous
power failure time is within 20ms when using 100 to 240VAC, or within 1ms when
using 24VDC.
Specifications
A985GOT-TBA(-EU),
A975GOT-TBA(-B)(-EU),
A970GOT-TBA(-B)(-EU),
A970GOT-SBA(-EU),
A970GOT-LBA,
A960GOT-EBA(-EU)
15)
3Hz
50VA or less (Using AC100V)
RS-422, RS-232C, Other
than Bus connection 69VA
63VA or less (Using AC200V)
RS-422, RS-232C, Other
than Bus connection 86VA
10MΩ or larger by insulation resistance tester
Transistor output, 2 points (RUN, OUTPUT)
Photocoupler insulation
12/24VDC
10.2 to 30VDC (Peak voltage 30V)
0.1A/point, 0.2A/common
0.4A, 10ms max.
0.1mA max.
1.0VDC (TYP.) 0.1A, 2.5VDC (MAX.) 0.1A
10ms max. (resistive load)
10ms max. (resistive load)
Zener diode
0.75 to 2mm
RAV1.25-3, V2-S3.3, V2-N3A, FV2-N3A
59 to 88N·cm
MELSEC-GOT
A985GOT-TBD (-V), A975GOT-TBD(-B),
A970GOT-TBD(-B), A970GOT-SBD,
A970GOT-LBD, A960GOT-EBD
24VDC (+25%,
40W
61A max. (30VDC, max. load)
1ms
By noise simulator of 500Vp-p noise voltage,
1µs noise width and 25 to 60Hz noise
frequency
500VAC for 1 minute across DC external
terminals and earth
2
20%)
3 - 8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A970gotA975gotA985got