2. Commissioning PROFIBUS−DP
2.3

Configuration with a Siemens master

2.3.1 STEP 7 HW Config (up to V 5.2)
GSD
2−10
Please note
Various configuration programs are available for use in
conjunction with a Siemens master. Please observe the
relevant procedure for your configuration program.
The following sections describe as an example the main con
figuration steps with the STEP 7 software. It is assumed that
the reader is already familiar with the information in the man
ual for the STEP 7 software.
Information on operation with general DP masters can be
found in A.2.
Preparations
1. Copy the GSD of the valve terminal into the directory
...\STEP7\S7DATA\GSD on your PC/programmer.
File: VI1000C9.GS*
(Reference sources for the GSD see section 2.2)
The GSDs can either be:
copied manually into the above mentioned directory
(e. g. with Windows Explorer) or
loaded via the menu [Options] [Install new GSD].
Please note
Update the hardware catalogue, if you copy the GSD
during work with STEP 7.
Menu HW Config: [Options] [Update catalogue]
Festo P.BE−CP−DI01−EN en 0503d