Festo CPV..-DI01 series Electronic Manual page 113

Valve terminal with direct connection
Hide thumbs Also See for CPV..-DI01 series:
Table of Contents

Advertisement

5. Diagnosis Festo field bus
LED
Colour
BUS
red
lights up
BUS
red
flashes fast
BUS
red
flashes slowly
(1−second
intervals)
BUS
flashes red
briefly out
Tab. 5/3:
Fault diagnosis with the red BUS LED
Festo P.BE−CP−DI01−EN en 0503d
Fault diagnosis with the red LED (BUS)
Operating status
Hardware fault
Field bus address not permitted
Field bus connection not OK.
Possible causes:
Station number not correct
(e.g. address assigned twice)
Field bus module switched off
or defective
Interrupted, short−circuited or
faulty field bus connection
Configuration not correct
Master configuration Setting
in the switch module
Switch module is missing
Switch module defective
Fault treatment
Servicing required
·
Correct address setting
·
(0, ..., 63)
Check the ...
address setting
·
field bus module
·
field bus connection
·
configuration of the master and
·
the setting in the switch module
Install switch module
·
Replace switch module
·
5−5