Short Circuit/Overload; Output Module - Festo CPV..-DI01 series Electronic Manual

Valve terminal with direct connection
Hide thumbs Also See for CPV..-DI01 series:
Table of Contents

Advertisement

3. Diagnosis PROFIBUS−DP
3.6

Short circuit/overload

3.6.1 Output module

3−24
Detailed information on input and output modules can be
found in the manual CP modules electronics."
In the event of a short circuit or overload
all the digital outputs of an output module will be
switched off.
the green LED Diag" on the output module will flash
quickly.
the bit short circuit/overload in octet 9 Device−related
diagnosis 2" will be set to logical 1.
Please note
The outputs cannot be used again until the short circuit or
overload has been eliminated and the fault deleted.
Festo P.BE−CP−DI01−EN en 0503d