Festo CPV..-DI01 series Electronic Manual page 40

Valve terminal with direct connection
Hide thumbs Also See for CPV..-DI01 series:
Table of Contents

Advertisement

1. Installation
M12 adapter (reverse key coded)
2
3
1
1
5
4
Bus in
Tab. 1/13: Pin assignment of the field bus interface with adapter for M12 connection,
5−pin
1−26
Connection with M12 adapter (reverse key coded)
With adapter (type FBA−2−M12−5POL−RK, part no. 533118),
you can connect the CPV Direct to the field bus via an M12
plug connector. The plug connectors have an inverted mech
anical coding (reverse key or B−coded), to avoid confusion
between incoming and continuing connections.
You can disconnect the M12 adapter from the CPV Direct
without interrupting the bus cable (T−TAP function).
Connection to the bus is made with a 5−pin M12 plug with
PG9 screw connector. Use the second connection socket for
the continuation of the field bus.
2
3
5
4
Bus out
Protective cap or plug with bus
termination resistor if connection
is not used.
Pin no.
1. VP: Power supply positive (P5V)
2. RxD/TxD−N: Receive/Send data N
3. DGND: Data reference potential (M5V)
4. RxD/TxD−P: Receive/Send data P
5. FE: Functional earth
Housing/thread: Screening/shield
Festo P.BE−CP−DI01−EN en 0503d

Hide quick links:

Advertisement

Table of Contents