3.3.

First power-on

At first power-on, after the controller has run the self-diagnostics test, press the
Menu. The parameters shown are a subset of all the controller parameters and let you rapidly configure the inputs and
outputs.
The number and type of the parameters shown depends on the controller HW configuration and on the choices made with
the parameters previously shown.
For example, minimum and maximum scale limits are shown only if you have chosen an mA or V type temperature sensor.
Fast Configuration also appears if the HMI menu is set to parameter QuiCk = On
3.3.1.

Fast configuration

> 2 s
> 2 s
> 2 s
A
40524-04 Rev0
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
Raises the value
Lowers the value
Raises the value
Lowers the value
A
3. COMMISSIONING
key to access the Fast Configuration
Home
Selecting sensor type
Selecting unit of measurement
The unit of measurement can be
°C or °F only if a TC or Rtd sensor is selected.
Minimum scale limit
Only if the selected sensor is in mV or V, the scale
limits LO.SCL, HI.SCL and the settable limits of the
LO.SP, HI.SP setpoint for TC or RTD sensors are
automatically set according to sensor type and unit
of measurement.
Maximum scale limit
Only if the selected sensor is in mV or V.
35