4.11.8. HYSTE - Hysteresis

Acronym
HYSTE
HYSTERESIS
IThe parameter shows and sets the hysteresis applied to the alarm setpoint value for the alarm being configured.
Unit of measurement:
Options:

4.11.9. DELAY - Alarm trip delay

Acronym
DELAY
DELAY OF ACTIVATION
The parameter shows and sets the alarm trip delay for the alarm being configured, i.e., the time that the value of the process
variable has to exceed the alarm setpoint for the alarm to trip.
This parameter prevents repeated alarms due to instantaneous and insignificant exceeding of that value.
If the parameter is set to "0.00" the alarm will be instantaneous, regardless of the time in which the process variable exce-
eds the alarm setpoint.
For a detailed explanation of this behavior, see paragraph "5.6.1. Generic alarms AL1...AL4" on page 142.
Unit of measurement:
Options:

4.11.10. MSG.AL - Message associated with tripping of alarm

Acronym
MSG.AL
SCROLLING MESSAGE AT ALARM ACT
The parameter shows and sets the number of the message associated with tripping of the alarm being configured, i.e.,
the scrolling message shown on the display.
For more information on scrolling messages, see paragraph "3.1.2.2. Scrolling messages" on page 34.
If the parameter is set to "0" no message will be displayed when the alarm trips.
The same message number can be assigned to different alarms
Unit of measurement:
Options:

4.11.11. BLK.AL - Flashing of PV display

Acronym
BLK.AL
BLINK DISPLAY PV DEF
The parameter shows and sets the flashing of the PV display in case of alarm, for the alarm being configured.
If the parameter is "On," the value shown on the PV display starts to flash in case of alarm.
Unit of measurement:
Options:
40524-04 Rev0
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
Scrolling message
Scale points
0...999
= For absolute (A.r.x = ABSLT) and symmetrical alarm (n.S.x = SYMMT)
-999...999
= For other types of alarms
Scrolling message
Minutes.seconds
0.00...99.59
Scrolling message
Message number
0...25
Scrolling message
-
OFF
= PV display does not flash in case of alarm
On
= PV display flashes in case of alarm
4. CONFIGURATION
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W
79