Ds.sp - Selecting The Sv Display; Ds.f - Selecting The F Display; Barg - Selecting The Bargraph Display - gefran 650 Abbreviated Manual

Hide thumbs Also See for 650:
Table of Contents

Advertisement

4.23.4. dS.SP - Selecting the SV display

Acronym
dS.SP
SV DISPLAY FUNCTION
The parameter shows and sets the display assigned to the SV display.
Unit of measurement:
Options:

4.23.5. dS.F - Selecting the F display

Acronym
dS.F
F DISPLAY FUNCTION
The parameter shows and sets the display assigned to the F display.
The parameter appears only if the controller is 1250 or 1350.
Unit of measurement:
Options:
note: if dS.SP = SETP and dS.F = OUT.PW
or dS.SP = OUT.PW and dS.F = SETP in manual operation
gradient GRAD.0 = 0: OUT.PW become MAN.PW
gradient GRAD.0 <> 0: SETP become MAN.PW
MAN.PW be changed via up / down if MAn.P = CHANGE

4.23.6. bArG - Selecting the bargraph display

Acronym
bArG
BARGRAPH FUNCTION
The parameter shows and sets the display assigned to the bargraph.
The parameter appears only if the controller is 1250 or 1350.
Unit of measurement:
Options:
40524-04 Rev0
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
Scrolling message
-
NONE
= NONE = Display off
SETP
= Local setpoint / manual power or active setpoint (read only), in case of Multiset function
SSP
= Active setpoint (read only)
IN.SPR = Remote setpoint input
OUT.PW = Power control output
SP-PV
= Deviation |SP-PV|
HEAT
= Heating power output with 0...100% control
COOL
= Cooling power output with 0...100% control
HE+CO = Power control output -100...100% (positive for heating, negative for cooling)
CURR1 = Current input CT1
CURR2 = Current input CT2
if the ENERG function is enabled:
CURR
= Load current
OUT.KW = Power on load
ENERG = Energy transferred to load
if the Timer function is enabled:
TIM.RE = Remaining timer value
TIM.EL = Timer value lapsed
if controller model with valve control:
V.POSI = Valve position
if controller model with programmer:
P.TIME = Current ramp time or retention step execution
Scrolling message
-
Same as dS.SP
Scrolling message
-
Same as dS.SP
4. CONFIGURATION
Submenu
Attributes
HMI
R W
Submenu
Attributes
HMI
R W
Submenu
Attributes
HMI
R W
125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

13501250

Table of Contents