ommissioning

Choice of binary outputs or process value input

Select using the jumpers:
2 binary outputs (see terminal Allocation when binary outputs selected) or
Process value input (see terminal Allocation when process value input selected)
Terminals 7 to 10 are connected to the corresponding signals.
terminal allocation on selection of binary outputs
Jumper
terminal allocation
7
8
9
10
terminal allocation on selection of process value input:
the input type is set via the configuration menu (see Procedure for specifying the basic settings).
Input type*
Jumper
4 ... 20 mA
internal
supply
Frequency
internal
supply
4 ... 20 mA
external
supply
Frequency
external
supply
Pt-100
(see
note
below)
note
For reasons of line compensation, connect the Pt 100 sensor over 3 conductors.
Be sure to bridge terminals 9 and 10 at the sensor.
terminal allocation with binary outputs
terminal allocation
11
Binary input +
12
Binary input GND
22 - 2702
Binary output 1
Binary output 1
Binary output 2
Binary output 2
termianl allocation
7
+ 24 V input transmitter
8
Output transmitter
9
Brigde to GND
10
GND
7
+ 24 V supply sensor
8
Clock input +
9
not connected
10
Clock input - (GND)
7
not connected
8
Process actual +
9
Process actual -
10
not connected
7
not connected
8
Clock input +
9
not connected
10
Clock input -
7
not connected
8
Process actual 1 (current supply)
9
Process actual 2 (compensation)
10
Process actual 3 (GND)
external connection
7
24 V / 0 V
8
GND
9
24 V / 0 V
10
GND
external connection
7
8
9
10
7
8
9
8
9
8
10
8
9
10
external connection
11
+
12
GND
NC / NO
NC / NO
+24 V
Clock +
Clock - (GND)
+ (4 ... 20 mA)
Clock - (GND)
Clock +
Clock - (GND)
Pt-100
0 ... 5 V (log. 0)
10 ... 30 v (log. 1)

Advertisement