9.
START-UP
9.1.
Safety instructions
WARNING!
Risk of injury from improper operation!
Improper operation may result in injuries as well as damage
to the device and the surrounding area.
▶ Before start-up, ensure that the operating personnel are
familiar with and have completely understood the contents
of the operating instructions.
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may start up the device/
the system.
9.2.
Start-up process
Before start-up, pneumatic, fluidic and electrical connections
must be established.
→
Switch on pilot pressure and supply voltage, keep the
process media switched off!
→
Remove the transparent cap of the controller to gain access
to the DIP switches or operating keys. Observe the special
instructions for potentially explosive areas.
→
Run the function X.TUNE for an automatic adjustment of
the positioner - see respective operating instructions for the
Type 869x used.
16
english
Type 2380
Start-up
→
For Type 8692/93: select the input signal (INPUT).
→
If necessary, specify additional controller settings (via DIP
switches/menu/USB adapter) - see respective operating ins-
tructions.
NOTE!
CAUTION with using the function SET.FACTORY
(reset to factory settings)!
This function does not only reset the settings implemented
by the user, but also all possibly preconfigured customer-
specific settings (referring to devices with additional label
„Customized Settings")
→
Switch on process media and activate set point.
→
If necessary, adjust the controller settings.
→
Tighten transparent cap of the controller again.
The device is now ready for operation.