1. Install field conduit dispenser per NFPA-70 along with any
state and local codes.
2. Pull field wiring allowing 72 inches of extra wire to reach upper
electrical enclosure.
3. Feed wire through conduit and into upper electrical enclosure
CAUTION: Do not damage wire while feeding through
conduit into the upper electrical enclosure.
4. Wrap some "CHICOX" fiber around wires and push into
conduit assembly to prevent potting from running down the
length of the conduit (see figure 40).
5. Using the wire separator provided, install one wire in each
hole until all wires are separated (see figure 41).
6. Push wire separator at least 3/4" into conduit.
7. Prepare potting compound according to directions.
NOTE: Use "CHICO A3" potting compound for sealing
fittings in hazardous locations.
8. Using a funnel, pour potting into conduit, be sure to get potting
in between each wire (see figure 41).
9. Let stand until firm.
10. Shorten field wiring to appropriate length when making
connections
11. Attach field wiring to terminal strip in upper electrical enclosure
according to the wiring diagram supplied for this dispenser
(see figure 42).
Potting Instructions
53
Figure 41 - Potting Instructions
Figure 42 - Wire Termination