Potting Instructions - Bennett 3700 Series Installation Manual

Commercial and retail dispensers. spec. 100 (2nd generation). remote dispensers and self-contained pumps
Hide thumbs Also See for 3700 Series:
Table of Contents

Advertisement

1. Install field conduit in the dispenser per NFPA-70 along with
any state and local codes.
2. Pull field wiring allowing 72 inches of extra wire to reach upper
electrical enclosure.
3. Feed wire through conduit and into upper electrical enclosure
CAUTION: Do not damage wire while feeding through
conduit into the upper electrical enclosure.
4. Wrap some "CHICOX" fiber around wires and push into conduit
assembly to prevent potting from running down the length of
the conduit (see figure 24).
5. Using the wire separator provided, install one wire in each hole
until all wires are separated (see figure 25).
6. Push wire separator at least 3/4" into conduit.
7. Prepare potting compound according to directions.
NOTE: Use "CHICO A3" potting compound for sealing
fittings in hazardous locations.
8. Using a funnel, pour potting into conduit, be sure to get potting
in between each wire (see figure 25).
9. Let stand until firm.
10. Shorten field wiring to appropriate length when making
connections
11. Attach field wiring to terminal strip in upper electrical enclosure
according to the wiring diagram supplied for this dispenser (see
figure 26).

Potting Instructions

37
Figure 25 - Potting Instructions
Figure 26 - Wire Termination
120001 Rev K 1-19-18

Advertisement

Table of Contents
loading

This manual is also suitable for:

3800 series37113724381138123822 ... Show all