Ecp Status Codes - Honeywell IntelliPath Series Installation And Setup Manual

High security internet and gsm communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

IGSMHS4G Installation and Setup Guide
PROMPTS
NOTE: Prompts 41 through 46 only appear if the Comm Path Choice is IP, or IP&GSM.
Use DHCP Y/N
41
(Y)_
NIC IP Address:
42
255.255.255.255_
Subnet Mask:
43
255.255.255.255_
Gateway IP Addr:
44
255.255.255.255_
DNS Serv IP Addr:
45
255.255.255.255_
Enable Pwr Save
46
(N)_
IP Connection
47
(Present)
Review? Y/N
48

ECP Status Codes

When the communicator is configured for ECP mode, it sends status messages to the control
panels for battery, power, tamper, and network connectivity failures. Some control panels
display these on the keypad as "LngRng Radio" followed by a 4-digit code (listed in the table
below). In addition, the Contact ID codes (listed in Appendix B) for these conditions are sent
to the central station by the communicator.
3-8
OPTIONS
[Y], [N]
Dynamically allocates the IP addresses (recommended); then skip to
Prompt 46: "Enable Pwr Save".
If [N], uses fixed IP addresses.
12 digit:
Enter the 4-part address for this device. The 4 parts of the address
must be separated by spaces (displayed as periods in Review mode).
xxx.xxx.xxx.xxx
Enter the 32-bit address mask used to indicate the portion (bits) of
12 digit:
the IP address that is being used for the subnet address. The 4 parts
xxx.xxx.xxx.xxx
of the address must be separated by spaces (displayed as periods in
Review mode).
12 digit:
Enter the 4-part address assigned to the Gateway. The 4 parts of the
address must be separated by spaces (displayed as periods in Review
xxx.xxx.xxx.xxx
mode).
12 digit:
Enter the 4-part IP address assigned to the DNS (Domain Name
System) server. The 4 parts of the address must be separated by
xxx.xxx.xxx.xxx
spaces (displayed as periods in Review mode).
[Y], [N]
To meet the 24 hour UL battery backup requirement, choose "Y" to
enable this feature. If this causes connectivity problems with certain
routers or switches, then choose "N" and wire the communicator so it
is plugged into a UL Listed UPS.
UL: Must be set to Y.
Press the [space] key to toggle between the options. Press [ENTER]
• Present
to select the configuration.
• Auto Detect
If "Present" is chosen, it is assumed that an IP is connected to the
device. If it is not detected, a Primary Comm Path Failure message
will be delivered after the programmed fault time expires.
If "Auto Detect" is chosen, the device will always try to use IP to
communicate but it will not generate a Primary Comm Path Failure
unless it previously detected the presence of IP. As soon as the
presence of IP is detected, a Primary Comm Path Restore message is
generated and the value of IP Connectivity programming parameter
is changed from "Auto Detect" to "Detected".
From this point on, the software expects connectivity. The auto
detect logic will resume only when the parameter is changed back to
"Auto Detect".
Reviewing Programming Mode Entries
[Y] = review
To review the programming options (to ensure that the correct
[N] = exit
entries have been made), press [Y]. The programming prompts are
displayed again. Use the up/down arrow keys to scroll through the
program fields without changing any of the values. If a value
requires change, simply type in the correct value. When the last field
is displayed, the "REVIEW?" prompt again appears.
To exit the programming mode, press [N] in response to the
"REVIEW?" prompt, and refer to Exiting Programming Mode at the
end of this section.