Wiring the Fault Relay
You may wire and program the communicator's fault output trigger for fail-safe mode (see
the prompt "FLT REL ON Y/N").
To sense a communicator fault at the control panel, see the figure below and make the
following connections. Include the proper EOL resistor required by the control panel.
UL
For Commercial Burglary, a 24 hour zone (supervisory) must be assigned on the control panel,
with the communicator's fault relay wired to that zone.
Wiring the Fault Relay to a Control Panel Zone for Normally Closed Fault
Internet Connection
• For UL installations, the Ethernet connection between the communicator and the router can-
UL
not exceed 12 feet with both the communicator and the router located within the same room.
•
Use a Listed cable / DSL router suited for the application.
Connect one end of the Ethernet cable to the communicator's RJ45 Ethernet connector and
the other end to the cable / DSL router as shown in the figure below.
Internet Connection
Section 2: Mounting and Wiring
2-5