Zone Trigger Mode; 4204 Mode And Two-4204 Mode; Supervision Features - Honeywell IntelliPath Series Installation And Setup Manual

High security internet and gsm communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

Zone Trigger Mode

• This mode is for use with control panels that do not support ECP communication nor 4204
Relay Modules
• The communicator provides six input zones and each zone can be configured for +V, -V, or
EOLR triggering.
UL – For the communicator, only the V+ inverted, V– non-inverted, and EOL options have
been evaluated.
• Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting
• Zone 1 input can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively
• Zone 1 can be programmed to report a LYNX panic (if used with LYNX control)
UL – This feature has not been evaluated by UL.
• Reports are sent in ADEMCO High-Speed format
UL

4204 Mode and Two-4204 Mode

• This mode is for use with Honeywell control panels that do not support ECP commu-
nication, but do support 4204 Relay Modules
• The communicator connects to the control panel's keypad terminals
• The control panel treats the communicator as 4204 Relay Module(s), so program the
control panel accordingly, including setting the communicator's proper 4204 device
address
• 4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
• Two-4204 mode provides up to eight zone inputs, depending on options programmed
• Each 4204 zone can be programmed for delayed reporting and restoral reporting
• Reports are sent in ADEMCO High-Speed format
UL

Supervision Features

The communicator provides the following types of supervision and fault detection:
• Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the communicator within a specified time, AlarmNet notifies
the central station of a communication failure.
• Communication path failure: In the event the module detects a communication path
failure, both the Central Station and the control panel can be notified of the trouble
condition. Both failures are considered true faults when the respective fault times have
expired ("GSM Fault Time" and "IP Fault Time" options) provided it has been set to a non-
zero value. Notification is sent to the central station upon this expiration. Notification to
the panel is controlled by the "Notify Panel Of" option.
(Note, if the "GSM Fault Time" and "IP Fault Time" options are set to zero, faults will not
be reported.)
• Fault output: Terminal 11 can serve as a fail-safe trigger for communicator fault
conditions.
If used, the fault relay will trip when the following conditions occur: tamper*, power loss*,
low battery*, battery charger fault*, loss of network connectivity*, the communicator is
not registered and the communicator is remotely disabled by AlarmNet.
* Alarm reporting for the noted conditions must be enabled for it to trigger the fault relay.
Opening and Closing ring back is supported by the control panel's digital dialer.
4204 Mode and Two-4204 Mode has not been evaluated.
Section 1: General Information
1-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Igsmhs4g

Table of Contents