Honeywell IntelliPath Series Installation And Setup Manual page 35

High security internet and gsm communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

PROMPTS
46
Restore Zn4 Y/N
(Y)_
Delay Zn4 (secs)
47
(00)
Rpt Zn4 ONLY if
48
Armed (N)_
Zn5 Trigger Type
49
(V+)_
Invert Zn5 Y/N
50
(N)_
Restore Zn5 Y/N
51
(Y)_
Delay Zn5 (secs)
52
(00)_
Rpt Zn5 ONLY if
53
Armed (N)_
Enable Zn6 Y/N
54
(N)_
Zn6 Trigger Type
55
(V+)_
Invert Zn6 Y/N
56
(N)_
Restore Zn6 Y/N
57
(Y)_
Delay Zn6 (secs)
58
(00)_
Rpt Zn6 ONLY if
59
Armed (N)_
Enable Zn7 Y/N
60
(N)_
Zn7 Trigger Type
61
(V+)_
4204/
ZONE
OPTIONS
TRIG.
2-4204
[Y], [N]
4
4
[01-15]
4
4
[00] = no
delay
[Y], [N]
4
2-
4204
only
• (EOLR)
4
• (V+)
• (V–)
[Y], [N]
4
[Y], [N]
4
2-
4204
only
[01-15]
4
2-
4204
[00] = no
only
delay
[Y], [N]
4
2-
4204
only
[Y], [N]
4204
only
• (EOLR)
4
4204
• (V+)
only
• (V–)
[Y], [N]
4
4204
only
[Y], [N]
4
4
[01-15]
4
4
[00] = no
delay
[Y], [N]
4
4
[Y], [N]
4204
only
• (EOLR)
4
4204
• (V+)
only
• (V–)
Section 3: Programming the Communicator
DESCRIPTION
Enables restore reporting for zone 4.
UL: Must be set to "Y."
Defines the reporting delay in seconds for
zone 4.
UL: Must be set to 00.
Reports alarms on zone 4 ONLY if the conditional zone
(zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is
triggered (armed).
If [N], always reports alarms on zone 4.
Selects the triggering method for this zone input. Press
the [space] key to scroll through choices.
UL: V+ must be set as inverted and V– as
non-inverted.
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 5.
UL: Must be set to "Y."
Defines the reporting delay in seconds for
zone 5.
UL: Must be set to 00.
Reports alarms on zone 5 ONLY if the conditional zone
(zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is
triggered (armed).
If [N], always reports alarms on zone 5.
Enables alarm reporting for zone 6.
If [N], skip to Prompt 60: "Enable Zn7."
Selects the triggering method for this zone input. Press
the [space] key to scroll through choices.
UL: V+ must be set as inverted and V– as
non-inverted.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
UL: Must be set to "Y."
Defines the reporting delay in seconds for
zone 6.
UL: Must be set to 00.
Reports alarms on zone 6 ONLY if the conditional zone
(zone 7 in zone trigger mode; zone 4 in 4204 mode; zone
8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 6.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 68: "Use DHCP."
Selects the triggering method for this zone input. Press
the [space] key to scroll through choices.
UL: V+ must be set as inverted and V– as
non-inverted.
3-17