IGSMHS4G Installation and Setup Guide
PROMPTS
Old Alarm Time
23
10 Minutes_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or IP.
IP Flt Time
24
(01 mins)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or GSM.
GSM Flt Time
25
(01 mins)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM.
Notify Panel Of_
26
(Both IP&GSM Flts)
Flt Rel ON Y/N
27
(N)_
Pwr Loss Rpt Y/N
28
(Y)_
Low Bat Rpt Y/N
29
(Y)_
3-6
OPTIONS
•10 Minutes
Sets how long an undeliverable alarm is retried for delivery to the
central station. If the message is not validated, it is retried until the
• 4 Hours
old alarm time is reached or the message is validated.
• 15 Minutes
Press the [space] key to scroll through choices.
• 8 Hours
• 30 Minutes
UL: Must be 10 minutes.
• 12 Hours
• 1 Hour
• 24 Hours
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[00-99]
In the event there is a loss of contact with the network over the
Ethernet connection, enter the time delay (in minutes) before the
communicator notifies the central station. IP failure will always be
sent to the central station as Primary Communication Path Failure.
UL: Must be one (01) minute.
In the event the communicator detects a communication path
[00-99]
failure, enter the time delay (in minutes) before the communicator
notifies the central station. A GSM failure will always be sent to the
central station as Secondary Communication Path Failure.
UL: Must be one (01) minute.
If "Both IP and GSM Faults" is selected, the device will only notify
[Both IP and
the control panel if both communication paths fail, but will always
GSM Faults]
send notification of either failure to the central station.
[Neither fault]
NOTE: The fault relay output (if programmed) will be triggered
only if "Both IP and GSM Faults" is selected.
(If the "GSM Fault Time" and "IP Fault Time" options are set to
zero, faults will not be reported.)
Press the [space] key to scroll through choices.
UL: Must be set to "Both IP and GSM Faults".
If enabled, the fault open collector output is normally energized to
[Y], [N]
ground, and de-energizes (open circuit) in the event of a
communicator fault. For conditions that trip the fault relay refer to
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring the Fault Relay in Section 2.
UL: Must be set to "Y."
Sends a primary power loss report to the central station within 1-3
[Y], [N]
hours after its detection. A restore report is sent within 1-3 hours
after power is restored.
UL Standard Installations (using transformer and battery): Must
be set to "Y".
Sends a low-battery report when a low battery condition exists. A
[Y], [N]
low battery restore is automatically sent when the low battery
condition clears.
UL Standard Installations (using transformer and battery): Must
be set to "Y".
DESCRIPTION