IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide
Wiring the 659EN Line Fault Monitor (Required for ULC)
The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS-
659EN), is installed. Note, the wire colors may vary.
1.
Refer to the installation guide for the 659EN.
2.
Mount the 659EN on the lower left side of the IPGSM-4GC cabinet.
3.
DO NOT cut the 659EN's BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper.
4.
Complete the interface wiring as shown below:
659EN
Example wiring for an addressable fire control panel:
IPGSM-4GC
Commercial Fire Communicator
YEL
ORG
RED
BLK
GRN
659EN
YEL
ORG
RED
BLK
GRN
4.7K, 1/2 watt
IPGSM-4GC
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
47K, 1/2 watt
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
Wire to a
Zone on the Fire Panel
FIRE LITE Addressable Fire Alarm Control Panel
MS-9050UD
TOP
MMF-300A
Monitor Module
T11
T10
T9
T8
T7
7 8 9
5 6
T6
4
3
2
1 0
15
TENS
LOOP
B+
TB2
B+ A+ B- A- A
– 6 –
- To next device
+ on SLC Loop
Braided-shield/Drain
Wire
T1
T2
T3
T4
7 8 9
5 6
10
4
T5
11
3
12
13
2
14
1 0
ONES
ADDRESS
B-
Shield
TB5
B
NO NC C
RELAY 1
SLC Loop
ALARM CONTACTS
IPGSM-4GC-014-V0