2: Primary And Secondary Phone Lines; 3: Communicator Fail Relay Driver; 4: Earth Ground; Specifications - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Specifications

The EIA-485 circuit cannot be T-Tapped and must be wired in a continuous fashion from the
control panel to the UDACT and, if installed, annunciators. The wire must be 12 to 18 AWG
twisted pair, shielded cable with a characteristic impedance of 120 Ohms, +/– 20%. Limit the total
wire resistance to 100 Ohms on the EIA-485 circuit. Do not run cable adjacent to, or in the same
conduit as 120 volts AC service, noisy electrical circuits that are powering mechanical bells or
horns, audio circuits above 25 volts RMS, motor control circuits, or SCR power circuits.
1.9.2 Primary and Secondary Phone Lines
Modular jacks are used to interface the primary and secondary phone lines to the public telephone
network.
1.9.3 Communicator Fail Relay Driver
Relay driver output for Central Station communication failure is available.
1.9.4 Earth Ground
An earth ground connection to the UDACT is required for transient protection. One option allows
connection via Earth Gnd terminal on TB3 using solid 12 AWG (3.25mm
lightning protection (this connection is not required when the UDACT is mounted in a grounded
metal enclosure via the upper right mounting hole).
A second option allows connection via the upper right corner mounting hole using a metal standoff
and screws, attach to grounded metal cabinet.
1.10 Specifications
1.10.1 DC Power
24VDC (nominal) filtered, non-resettable and power-limited. DC Power at terminal block TB1
(+, –) is 40 mA in standby, 75 mA maximum while communicating and 100 mA with the open
collector output engaged and communicating.
1.10.2 Data Communications
EIA-485 Serial Interface, terminal block TB1 (RS+, RS–, Shield, RS+, RS–). Power-limited
source must be used. The terminals marked "TERM RS+, RS–" are for future use.
1.10.3 Auxiliary Output
TB3 Communicator Failure. An Open Collector type output, normally high, active low which sinks
up to 40 mA. TB3 (+24V), power-limited. Use UL listed relay P/N: MR-101/C or MR-201/C with
this output.

1.11 Telephone Requirements and Warnings

NOTE: The FCC ID label is located on the inside of the door of the host panel
The FCC ID label is located on the inside cover of the remote backbox.
UDACT Instruction Manual — P/N 50050:M 12/18/2009
or
Overview
2
) wire to provide
13

Advertisement

Table of Contents
loading

Table of Contents