IntesisBox
BACnet/IP Server - KNX
•
Read from file: BDT will be overwritten by the last BDT saved in LinkBoxBacnet file
"KNX.ini".
•
Write to file: BDT will be saved in LinkBoxBacnet file "KNX.ini".
•
Read from GW: BDT will be overwritten by the BDT currently used by IntesisBox.
This button will be disabled if IntesisBox is not connected to LinkBoxBacnet.
•
Write to GW: BDT will be written to the IntesisBox and from that moment
Intesisbox will use this BDT for BBMD functionality. Bear in mind that IntesisBox's
BDT can be overwritten by BACnet means.
This button will be disabled if IntesisBox is not connected to LinkBoxBacnet
5.1.4 Saving the configuration
When the configuration of the project is finished follow the next steps:
1. Click the button Save. Once accepted the pop-up message, that will save the project
in the folder on hard disk (more information in LinkBoxBacnet Manual).
2. You will be prompted to generate the configuration file to be sent to the gateway,
a. If YES is selected, the binary file (KNX.LBOX) containing the configuration for
the gateway will be generated and saved also into the project folder.
b. If NO is selected the binary file needs to be created before following the next
steps. To do so open the Configuration window (section 5.1) and restart from
step 1
3. A pop-up message will show up asking if you want to preserve the Object
instance numbers. BE CAREFUL using this feature.
a. If NO is selected all the object instance numbers for the points will be
automatically reconstructed and thus loosing previous instance numbers, if
defined. ONLY USE this option for a brand new configuration not
previously running in the gateway and therefore not yet integrated into the
BACnet system
b. Select Yes for configurations previously running in the gateway and
already integrated into the BACnet system that had been extended with
a few more points that must respect the previously defined object
instance numbers. All the points with object instance numbers defined will
be respected. LinkBoxBacnet will automatically assign object instance
numbers to ones without it.
4. As the final step, a pop-up message will ask if you want to see the BACnet points list
report, If you select Yes, a text file called KNX- BACNET OBJECT LIST.TXT will be
generated and saved into the project folder containing a report of all the point's
BACnet information (for informative purposes at user level). The file will be also
opened in the notepad, it looks like this:
ObjIdent
12582912
00000000
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
ObjType
OInst ObjName
3-BI
0000 BUS_KNX_ERR_COM
0-AI
0000 AI_01_0_013 Test object AI
User's Manual r18 eng
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
25 / 31