Aa0H( Data ) - ICP DAS USA I-7080 User Manual

Network data acquisition and control modules
Hide thumbs Also See for I-7080:
Table of Contents

Advertisement

2.11
$AA0H(data)
: Set the min. input signal width at high level. Refer to
Description
Sec. 1.8.5 for more information.
: $AA0H(data)[chk](cr)
Syntax
$ is a delimiter character
AA=2-character HEX module address, from 00 to FF
(data)=5-character decimal value for min. width at high level.
The unit is uS and the range can be from 2 uS to 65535
uS.
[chk]=2-character checksum, if checksum disable
(cr)=0x0D
: valid command
Response
invalid command
no response
or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
(cr)=0x0D
Example
:
command: $010H00010(cr)
response : !01(cr)
command: $020H01000(cr)
response : !02(cr)
I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 35
!AA[chk](cr)
?AA[chk](cr)
syntax error or communication error
Min. width = 10 uS
Min. width = 1000 uS = 1 mS
7080/7080D
no [chk]
no [chk]

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-4080dI-7080bI-4080

Table of Contents