ICP DAS USA I-7080 User Manual page 42

Network data acquisition and control modules
Hide thumbs Also See for I-7080:
Table of Contents

Advertisement

2.18
$AA2
: Read the configuration of module.
Description
: $AA2[chk](cr)
Syntax
$ is a delimiter character
AA=2-character HEX module address, from 00 to FF
[chk]=2-character checksum, if checksum disable
(cr)=0x0D
: valid command
Response
invalid command
no response
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
TT, CC, FF: refer to Sec. 1.9
[chk]=2-character checksum, if checksum disable
(cr)=0x0D
Example
:
command: $012(cr)
response : !01500600(cr)
command: $022(cr)
response : !02510700(cr)
NOTE: If the user use %AANNTTCCFF command to change module
configuration, the new configuration code will be stored into
EEPROM immediately. The configuration code includes module
address, module type, baud rate code, checksum enable/disable code,
calibration code, power-on value and safe value. The EEPROM data
of I-7000 can be read infinite times and can be written about
100,000 times max. Therefore the user should not change
configuration code often for testing.
The $AA2 command is used to read EEPROM data only, therefore the
user can send this command to I-7000 module infinitely.
I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 42
7080/7080D
!AATTCCFF[chk](cr),
?AA[chk](cr)
syntax error or communication
Address=01, counter, 9600 BPS,
checksum disable
Address=02, frequency, 19200 BPS,
checksum disable
no [chk]
no [chk]