1.6

Quick Start

Refer to "I-7000 Bus Converter User Manual" chapter-5 for
the following functions:
module status unknown(Sec. 5.1), change address(Sec. 5.2)
change baud rate(Sec. 5.3), checksum enable/disable(Sec. 5.4)
Wire connection(Sec 2.4)
Test program TEST.EXE(Refer to "NAP7000S User
Manual" for details.
1.6.1
Frequency Input Measurememt
1. Refer to Sec. 1.5.2 for wire connection. Power on and run test.exe
2. press 2
3. press $012[Enter]
4. press 2
5. press %0101510600[Enter]
6. press 2
7. press $01B0[Enter]
8. press 2
9. press #010[Enter]
10. press 2
11. press #011[Enter]
step 3: the status of I-7080 is COUNTER mode
step 5: change to frequency mode
step 7: select non-isolated input
step 9: frequency measurement of channel-0
step 11: frequency measurement of channel-1
Note: the command $01B1(step 7) can be used to select the iso-
lated input.(the command $01B2 and $01B3 are used for
the other selections)
I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 12
Receive=!01500600
Receive=>!01
Receive=!01
Receive=>????????
Receive=>????????