1.8.3
Digital Output Application Notes
The D/O0 & D/O1 can be used as D/O or alarm output as
following:
• can be used as D/O in the frequency mode.
• can be used as D/O in the counter mode & alarm disable
(by @AADA or @AADAN command)
• can be used as alarm output in the counter mode & alarm
enable(by @AAEAT or @AAEAN command)
Frequency mode
Counter mode & alarm disable
Counter mode & alarm enable (alarm
mode 1, ~AAA1)
Counter mode & alarm enable (alarm
mode 0, ~AAA0 & @AAEA0)
Counter mode & alarm enable (alrm
mode 0, ~AAA0 & @AAEA1)
Programmable Threshold Voltage Setting
1.8.4
The programmable threshold voltage is valid for non-
isolated input of counter mode (50) & frequency mode(51).
The default setting are given as following:
TTL compatible
low trigger level = 0.8 volt
high trigger level = 2.4 volt
The high trigger level can be changed by $AA1H(data)
command, the low trigger can be changed by $AA1L(data)
comand. The high trigger level must be greater than the low
trigger level.
I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 16
D/O 0
D/O 1
D/O 0
D/O 1
D/O 0
D/O 1
High-alarm
High-high alarm
on counter 0
on counter 0
Alarm on
D/O 1 or alarm
counter 0
on counter 1
D/O 0 or
alarm on counter
alarm on
1
counter 0