Gate Control Setting
1.8.6
The gate control will be ignored in frequency mode(51).
The gate control is defaultly disable in counter mode(50). The
user can use command to enable/disable the gate control as
following:
$AAA0
$AAA1
$AAA2
Preset Value Setting
1.8.7
The preset value will be ignored in frequency mode(51).
The counters will go to their preset value in the first power-on
state. The reset counter command, $AA6N, also force the
counters go to their preset value. The factory default setting of
preset value is 0. The user can use the $AAPN(data) command
to change the preset value. The key points are given as
following:
Factory default setting
Power on state
$AA6N
$AAPN(data)
I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 18
gate input must be low to enable counter
gate input must be high to enable counter
gate input is ignored. The counter will be
always enable.
I-7080 & I-7080D
Counter preset value is 0
Counter 0/1 go to preset value
Counter N go to preset value
Set preset value of counter N