Connection to the Master System (ModBus Standard)
Input register (Read) (continuation)
Adress
Description
3x0078
3x0079
3x0080
3x0081
3x0082
3x0083
3x0084
Outdoor air humidity - relative
3x0085
Outdoor air humidity - absolute
3x0086
Outdoor air humidity - enthalpy
3x0087
Inlet air humidity - relative
3x0088
Inlet air humidity - absolute
3x0089
Inlet air humidity - enthalpy
3x0090
Room air humidity - relative
3x0091
Room air humidity – absolute
3x0092
Room air humidity - enthalpy
3x0093
Dew point
3x0095
Inlet air flow rate
3x0096
Outlet air flow rate
3x0097
Inlet air flow rate
3x0098
Outlet air pressure
3x0099
3x0101
Air quality
3x0102
3x0104
Act heating stpt
3x0105
Act cooling stpt
3x0106
Act sply htg stpt
3x0107
Act sply clg stpt
3x0108
Current required value of humidity -
humidification
3x0109
Current required value of humidity -
dehumidification
3x0110
Current humidification required value for
cascade control
3x0111
Current dehumidification required value in
cascade control
3x0112
Act sply fan stpt
Control units VCS
Values/Units
%r.H.
`-x.y - +x.y g/kg
`-x.y - +x.y kJ/kg
%r.H.
`-x.y - +x.y g/kg
`-x.y - +x.y kJ/kg
%r.H.
`-x.y - +x.y g/kg
`-x.y - +x.y kJ/kg
`-x.y - +x.y g/kg
0 - x m3/h
0 - x m3/h
0 - x Pa
0 - x Pa
0 – x ppm
`-x.y - +x.y °C
°C
°C
°C
0 - x.y %r.H.
%r.H.
%r.H.
%r.H.
0-100% (0 - x l/s)
Remarks
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)
(divider 10)