Control (HMI-DM,HMI-TM controllers)
HMI-DM (HMI-TM) control devices ensure communication
between the VCS control unit and the user. Th ey are intended
for air-handling device control, handling and service. Th e HMI
control device can be connected to the POL4xx or POL6xx
controllers. During controller operation, a single HMI control
device can be connected or disconnected and alternatively (in
sequence) used to control multiple control units (controllers).
Connection
Th e HMI-DM controller can be connected using a serial inter-
face (4-wire, twisted pair) with two RJ45 connectors. Th e
cable length is 1.5 m (the cable is included in the delivery).
When installed on a wall, the HMI-DM controller can be con-
nected using a shielded 8-wire UTP cable with two RJ45
connectors. Th e maximum distance is up to 50 m.
Th e HMI-TM controller can be connected to the control unit
using a 4-wire cable (twisted pair) with one RJ45 connector
and one slim connector. Th e cable length is 2.5 m (the cable
is included in the delivery).
Warning
Aft er connecting the controller to the control unit, it is nec-
essary to route the cable through the PG16 grommet. Th us
degree of protection IP20 is ensured. If a higher level of protec-
Figure 22
HMI-DM controller
Operating conditions
Degree of protection: IP 31. Permissible ambient temperature:
-40 °C to 70 °C. Relative humidity <95 %.
Device Description
Th e controller consists of two separate parts – the face plate
with a display and the rear plate. Dimensions of the HMI-DM
controller are 144x96x26 mm and the integrated LCD display
resolution is 208x96 pixels. Th e display can show 8 lines. Th e
HMI-DM controller is equipped with three function buttons,
INFO, FAILURE and ESC, and one scrolling knob. The
scrolling knob and buttons are used to navigate within the
menu and to change the parameters and control values. Th e
INFO, FAILURE and ESC buttons are equipped with LEDs to
indicate operating states.
Th e controller can also be delivered in a version for free loca-
tion. Th e magnets on the rear side of the HMI enable the con-
troller to be attached to metal parts (e.g. the air-handling unit).
48
tion of the distribution board cas-
ing is required, the grommet will
have to be resealed. An optional
grommet with an RJ 45 connector
can be used to make it easy to con-
nect (disconnect) the HMI control-
ler (an extra order is required, not
included in the standard delivery).
Th en the RJ45 connector must
be connected to the RJ45 socket
on the controller. For the socket
marking, see the fi gure.
Figure 23 – HMI-DM cotroller
Info
Failure
For fi xed mounting, the controller is equipped with threaded
holes on its rear side to screw it to the mounting plate.
Table 1 – Function Buttons
Button
Activity
(Name)
Turning
Press
Scrolling
knob
Hold
Press
Esc
Hold
Press
Info
Flashing
green
Green light
Press
Failures
Flashing
red
Red light
ESC
Scrolling knob
Description
- Selection from the menu
- Selection from the param-
eters or change to a value
- Selection/confi rmation
- When logged in, press and
hold for at least 3 s to go to
the log-in/log-out page.
- When not logged in at any access
level, the log-in page is displayed.
- Cancels the change to
the parameter value
-Returns to the upper level of
the menu/previous page
- Returns to the last active page
before accessing the Pass-
word Administration page
- Returns to the last active page
before accessing the Home
page using the Info button.
- Goes to the Start Menu
- Goes to the Main Menu from
the current menu page
- Goes to the Start Menu
page from the Main Menu
- Air-handling unit start-up sequence
- Air-handling unit operation
- Every time you press this button,
you will cycle through the following
pages → List of Failures → His-
tory of Failures → Alarm Settings
(failure confi rmation and reset)
- Active unconfi rmed failures
- Active confi rmed failures