Electronic Expansion Valve Overheating Controller EC3-X33
ECD-002 Display with Buttons (LED Indicators and Settings)
Flashes: The valve closes.
On: The valve opens.
On: Command to run
Off: N/A
Flashes: Exhaust
On: Alarm
Off: N/A
Settings of Main Parameters on ECD-002
(before start)
Make sure the digital input I is without voltage, then it is pos-
sible to connect the terminal to 24V.
Important: When the digital input is switched off (0V), the
main parameters will be set as follows: Coolant Type (u0),
Pressure Sensor Type (uP) and Valve Type (ut).
These parameters must be set at voltage of 0V to prevent
damage to the valve or compressor due to the transfer of the
setting changes to the controlled element.
To make it easy, the setting procedure is described at the
end of this manual. Once these parameters have been set
and saved, the other functions can be set during operation.
Start-up
Start the system and verify it for proper overheating settings.
The EC3-X33/53 controller can work even without the con-
nected ECD-002 display. The ECD is mainly used to set the
desired actions.
Setting Procedure using ECD-002
The device settings are protected by a digital code. The de-
fault factory setting is "12". To enter the program, proceed
as follows:
- Press and hold the PRG button for more than 5 seconds, 0
will start flashing.
- Using the
or
buttons, set 12 as the password and press
the SEL button to confirm.
- Then the first parameter (/1) to be set is displayed. Change
the settings using the procedure below:
- Using the
or buttons, select the parameter code to be
changed.
106
Flashes: The valve opens.
On: The valve is open
Settings: Parameter
Prg & Sel (5 sec)
Manual reset
of the flashing code
Parameter selection
- Press the
or
button to increase or decrease the value.
- Press the SEL button to confirm the new value and continue
to the next parameter.
The process still repeats: "press the
display..."
To exit the parameter change mode
Press the PRG button to confirm the new values and close the
setting process of the newly changed parameters.
To exit without changing any parameter:
Do not touch any button for the next 60 seconds (time for
setting will elapse).
Reset – Recovery of Default Factory Settings
- Make sure the digital input is without voltage (0V).
- Simultaneously press the
seconds, "0" will display.
- Using the
or
button, set the password "12" and press
the SEL button to confirm.
- If a different password is used, this new password is set
and A0 will appear.
- Press the SEL button to reset the device – the default factory
settings will be restored.
- Press the PRG button to exit and save the default factory
settings
Valve Build-Up Time at Start (parameters uu and u9)
Increases
Scrolls
Decreases
value
or
to set on the
and
buttons for more than 5