List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
268 S
The signal voltage request of START (Toshiba)
Cooling
393
A
394 U
Outdoor temperature to enable cooling – all versions
395
A
396 U
Minimum pump operating time – water version
397
A
398 U
Pump downtime to the pump turning activation – water version
399
A
401 U
Active pump turning time – water version
Minimum operating time, single-stage condensing unit – version with
397
A
398 U
single-stage condensing unit
399
A
401 U
Re-cooling blocking time – versions with single-, two-stage condensing units
Retention time during transition from Stage 1 to Stage 2 – version with
402
A
403 U
two-stage condensing unit
Cooling request dependent evaporator Stage 1 switch-on – version with
404
A
405 U
two-stage condensing unit
Cooling request dependent evaporator Stage 2° switch-on – version with
406
A
407 U
two-stage condensing unit
408
A
409 U
Hysteresis for transition from Stage 1 to Stage 2, two-stage condensing unit
410
A
411 U
Minimum inverter operating time – version with inverter
Inverter re-start blocking time – version with single-stage condensing
412
A
413 U
unit + inverter
413
A
AO cooling signal inversion
Water heating with pre-heating function
Outdoor temperature-dependent pump start-up in the AHU Stop and
414
A
415 U
Run mode
416
A
417 U
Minimum pump run time
418
A
419 U
Pump downtime to the pump turning activation
420
A
421 U
Active pump turning time
422
A
423 U
Active function preheating of water operation time
424
A
425 U
Pre-heating function blocking time between AHU unit shut-down and restart
426
A
427 U
Water heater circuit heating curve setting at the AHU start-up X1
428
A
429 U
Water heater circuit heating curve setting at the AHU start-up Y1
430
A
431 U
Water heater circuit heating curve setting at the AHU start-up X2
432
A
433 U
Water heater circuit heating curve setting at the AHU start-up Y2
434
A
435 U
Stop to Run mode switching delay AP trigger value
436
A
437 U
Water heat exchanger dependent AP trigger value – AHU in Run mode
438
A
439 U
Water heat exchanger dependent AP trigger value - AHU in Stop mode
440
A
441 U
Inlet air dependent AP evaluation enabling delay after the unit start-up
442
A
443 U
Inlet air temperature dependent AP start-up – failure alarm A
444
A
445 U
Inlet air temperature dependent AP start-up
446
A
447 U
Maximum return water temperature
Water pre-heating
448
A
449 U
Outdoor dependent pre-heating (pump) start-up
450
A
451 U
Pump downtime to the pump turning activation
452
A
453 U
Active pump turning time
454
A
455 U
Minimum pump run time
Heating water source switching
456
A
457 U
Limit value for heating
458
A
459 U
Start-up sequence delay
Gas heating
460
A
461 U
Cooling sequence enabling
462
A
463 U
Minimum burner run time
464
A
465 U
Minimum burner downtime
466
A
467 U
Burner restart protection time (burner Stage 1)
468
A
469 U
Modulation burner opening/closing speed (burner Stage 1)
470
A
471 U
Heating request value for the burner Stage 2 switch-off
472
A
473 U
Maximum flue-gas temperature setting for alarm
474
A
475 U
Maximum flue-gas temperature
476
A
477 U
Requested flue-gas temperature
478
A
479 U
Minimum flue-gas temperature
Electric heating
480
A
481 U
Electric heating switching on – request for heating
482
A
483 U
Electric heating hysteresis
Control units VCS
Menu HMI-SG
Meaning
0
Switched OFF
1
Switched ON
0 without cooling
1 with cooling
Factory Settings
Value
Min
Max
8
0
10
V
12
-64
64
°C
180
0
9999
s
168
0
9999
h
60
0
9999
s
60
0
9999
s
120
5
600
s
360
5
600
s
20
0
100
%
70
0
100
%
10
0
20
%
10
0
9999
s
60
0
300
s
5
-64
64
°C
180
0
9999
s
168
0
9999
h
60
0
9999
s
120
0
600
s
5
0
30
min
-10
-30
5
°C
100
0
100
%
10
0
50
°C
10
0
100
%
60
0
600
s
15
0
50
°C
30
0
50
°C
60
0
600
s
6
-64
64
°C
8
-64
64
°C
70
20
140
°C
5
-50
15
°C
168
0
9999
h
30
0
9999
s
30
0
9999
s
15
5
25
°C
120
10
600
s
150
0
600
s
150
0
600
s
150
0
600
s
5
0
20
%/s
40
10
100
%
230
210 400
°C
210
160 p.472
°C
160
150 210
°C
150
100 160
°C
20
0
100
%
10
1
100
%
37