List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
Mixing
484
A
484
U
Minimum fresh air value setting
484
A
484
U
Minimum fresh air value setting – Comfort mode (pool unit)
485
A
485
A
Minimum fresh air value setting – Economy mode (pool unit)
484
A
485 U
Minimum fresh air flow rate setting
486
A
487 U
Starting temperature for mixing damper wide-open position
488
A
489 U
Starting time for mixing damper wide-open position
490 U
Mixing damper control signal recurrence vale (normal/inverse)
Max. limit of fresh air function (ventilation unit)
563 A
564
U
Max. limit of fresh air according to T outdoor
565 A
566
U
T outdoor from which the Max. limit of fresh air is activated
567
U
Information about the Max. limit of fresh air activation
491
A
492 U
Required temperature for pre-heating
493
A
494 U
Outdoor dependent electric pre-heating blocking
495
A
496 U
Heating request dependent el. –pre-heating switch-on
497
A
498 U
Hysteresis for electric pre-heater switch-off
Electric reheating
502
A
503 U
Heating request dependent electric re-heating start-up for Stage 1
504
A
505 U
Hysteresis for electric re-heating switch-off
506
A
507 U
Fan stage dependent outlet limitation ST1
508
A
509 U
Fan stage dependent outlet limitation ST2
510
A
511 U
Fan stage dependent outlet limitation ST3
512
A
513 U
Fan stage dependent outlet limitation ST4
514
A
515 U
Fan stage dependent outlet limitation ST5
Heat recovery
516
A
517 U
Freezing determination temperature exchanger
518
A
519 U
Start temperature for maximum - HRE speed/volume open BP PE
520
A
521 U
Start time for maximum - HRE speed/volume open BP PE
522
A
523 U
Heat recovery request dependent HRE run enabling
524
A
525 U
Hysteresis for HRE run stop
526 U
Information - antifreeze protection start-up
Night turning
527
A
528 U
Time to next turning
529
A
530 U
Active turning time
Humidification
531 A
532 U
Relative set-point of relative humidity - Comfort
535 A
536 U
Relative set-point of humidity - Economy
541 A
542 U
Humidification blocking in summer
545 U
Humidification output
550 G
Calculated current humidification set-point in the cascade
Dehumidification
533
A
534
U
Dehumidification relative set-point - Comfort
537
A
538
U
Dehumidification relative set-point - Economy
533
A
534 U
Dehumidification required relative value
537
A
538 U
Dehumidification required absolute value
539
A
540 U
Maximum humidity required value
543 U
Current humidity value
544 U
Maximum humidity
546 U
Dehumidification output
547 U
Dew point
548
A
549 U
Dew point deviation
551 G
Calculated current dehumidification required value for cascade control
Humidity-dependent fan speed compensation
552
A
553 U
Humidity required value for compensation
554
A
555 U
Fan speed compensation function
38
Menu HMI-SG
Meaning
0
Inactive
1
Active
0 inactive
1 active
0
Ne
1
Ano
0 increase
Factory Settings
Value
Min
Max
20
0
100
%
20
0
100
%
20
0
100
%
20
0
100
%
15
-64
64
°C
60
0
600
s
100
0
100
%
40
0
100
%
-10
-100 100
°C
-20
-50
10
°C
-30
-50
10
°C
20
0
100
%
10
0
100
%
20
0
100
%
10
1
100
%
100
0
100
%
100
0
100
%
100
0
100
%
100
0
100
%
100
0
100
%
1
-64
64
°C
15
-64
64
°C
60
0
600
s
38
0
100
%
5
0
100
%
3
0
9999
h
300
0
9999
s
40
0
100
%r.H.
30
0
100
%r.H.
0
%
60
0
100
%r.H.
70
0
100
%r.H.
60
0
100
%r.H.
12
0
100
g/kg
80
0
100
%r.H.
%
%
°C
1
-64
64
°C
%r.H.
50
0
100
%r.H.
0