List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
198
S
198 S
Air quality dependent fan speed compensation
199
S
199 S
Room (outlet) temperature dependent fan speed compensation
230
S
230 S
Humidity-dependent fan speed compensation
231
S
231 S
Limitation of dehumidification during heating
201
S
201 S
Difference between required and actual temperature monitoring
202
S
202 S
Air quality dependent damper position compensation
246 S
246 S
Humidity-dependent mixing damper position compensation
247 S
247 S
Max. limit of fresh air according to T outdoor (ventilation unit)
203
S
203 S
Cooling using HR (RHE, BP PE, mixing damper)
Heating/cooling dependent fan speed compensation-cooling sequence
204
S
204 S
(fan, cooler)
205
S
205 S
Mixing heating sequence (damper, heater)
206
S
206 S
Night cooling
207
S
207 S
Temperature start-up
208
S
208 S
Time mode start optimization
209
S
209 S
Damper and outlet fan blocking
210
S
210 S
Outlet fan correction type (TRN controllers)
211
S
211 S
Reset after configuration of additional modes/functions
212
S
212 S
Room temperature measuring point selection
Control signal characteristic
213
A
213 A
Control signal 0-10 V or 2-10 V, heating
214
A
214 A
Control signal 0-10 V or 2-10 V, cooling
215
A
215 A
Control signal 0-10 V or 2-10 V, mixing damper
Control units VCS
Menu HMI-SG
Meaning
3 Heating + Cooling
0 No
1 Yes
0 No
1 Yes
0 No
1 Yes
0 No
1 Yes
0 No
1 inlet
2 room
3 Inlet+room
0 No
1 Yes
0 No
1 Yes
0 No
1 Yes
0 without HR cooling
1 RHE, BP PE
2 mixing damper
3 RHE+ damper
0 fan+cooler
1 cooler+fan
0 damper+heater
1 heater+damper
0 without chilling
1 with chilling
0 N/A
1 heating
2 cooling
3 heating + cooling
0 N/A
1 heating
2 cooling
3 heating + cooling
0 N/A
1 dampers
2 dampers+fan
0 separate stages
1 shared stages
0 without reset
1 reset
0 average
1 minimum
2 maximum
3 room temp. sensor 1
4 room temp. sensor 2
5 HMI-SG 1 controller
6 HMI-SG 2 controller
0 0-10V
1 2-10V
0 0-10V
1 2-10V
0 0-10V
1 2-10V
Factory Settings
Value
Min
Max
1
0
0
0
0
0
0
0
3
1
0
0
0
0
0
3
1
1
1
33